NOTICE
If a time threshold has been parameterized, the Vdc_max controller should also be activated (p1280 = 3) so that the
drive does not shut down with overvoltage when Vdc_min control is exited (due to the time violation) and in the event
of fault response OFF3. It is also possible to increase the OFF3 ramp-down time p1135.
p1296[0...n]
Vdc_min controller response (kinetic buffering) (U/f) / Vdc_min response
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the response for the Vdc_min controller (kinetic buffering).
Value:
0:
1:
Note
For p1296 = 1:
The quick stop ramp entered in p1135 must not be equal to zero, to prevent overcurrent shutdown if F07406 is triggered.
p1297[0...n]

Vdc_min controller speed threshold (U/f) / Vdc_min n_thresh

Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Sets the speed threshold for the Vdc-min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized .
Note
Exiting the Vdc_min control before reaching motor standstill prevents the regenerative braking current from increasing
significantly at low speeds, and after a pulse inhibit, means that the motor coasts down.
r1298

CO: Vdc controller output (U/f) / Vdc_ctrl output

Access level: 3
Can be changed: -
Unit group: 3_1
Min:
- [rpm]
Description:
Displays the actual output of the Vdc controller (DC link voltage controller)
p1300[0...n]

Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode

Access level: 2
Can be changed: C2(1), T
Unit group: -
Min:
0
Description:
Sets the open and closed-loop control mode of a drive.
Value:
0:
1:
2:
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Buffer Vdc until undervoltage, n<p1297 -> F07405
Buff. Vdc until undervolt., n<p1297 -> F07405, t>p1295 -> F07406
U/f control with linear characteristic
U/f control with linear characteristic and FCC
U/f control with parabolic characteristic
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Scaling: -
Unit selection: p0505
Max:
210000.00 [rpm]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max:
20
Parameters
7.2 Parameter list
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
50.00 [rpm]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6320, 6854
Factory setting:
- [rpm]
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: 6300, 6301,
6851, 8012
Factory setting:
0
667