Speed_Ctrl_Opt Vibration Test Vibration Frequency Determined; Speed_Ctrl_Opt Saturation Characteristic Rotor Flux Maximum; Polid Technique / Polid Technique; Co/Bo: Polid Diagnostics / Polid Diag - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
r1970[0...1]
Speed_ctrl_opt vibration test vibration frequency determined / n_opt f_vib det
Access level: 4
Can be changed: -
Unit group: -
Min:
- [Hz]
Description:
Displays the vibration frequencies determined by the vibration test.
Index:
[0] = Frequency low
[1] = Frequency high
Dependency:
See also: p1959
See also: F07985
p1974
Speed_ctrl_opt saturation characteristic rotor flux maximum / n_opt rot_fl max
Access level: 4
Can be changed: T, U
Unit group: -
Min:
104 [%]
Description:
Sets the maximum flux setpoint to measure the saturation characteristic.
p1980[0...n]

PolID technique / PolID technique

Access level: 3
Can be changed: T, U
Unit group: -
Min:
1
Description:
Sets the pole position identification technique.
p1980 = 1, 8: The current magnitude is set using p0329.
p1980 = 4, 6: The current magnitude of the first measurement section is set using p0325, the second using p0329.
p1980 = 10: The rated motor current is impressed to align.
The current magnitudes are limited to the rated power unit values.
Value:
1:
4:
6:
8:
10:
Dependency:
See also: p1780
See also: F07969
Note
Voltage pulse technique (p1980 = 1, 4, 8) cannot be applied for operation with sine-wave output filters (p0230).
r1992.0...15

CO/BO: PolID diagnostics / PolID diag

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for the diagnostics information of the pole position identification (polID)
Bit field:
Bit
730
Voltage pulsing 1st harmonics
Voltage pulsing 2-stage
Voltage pulsing 2-stage inverse
Voltage pulsing 2nd harmonic, inverse
DC current injection
Signal name
Calculated: -
Scaling: -
Unit selection: -
Max:
- [Hz]
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
120 [%]
Calculated: CALC_MOD_REG Data type: Integer16
Scaling: -
Unit selection: -
Max:
10
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
- [Hz]
Dynamic index: -
Function diagram: -
Factory setting:
120 [%]
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
4
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
SINAMICS G120X converter

Advertisement

Table of Contents
loading

Table of Contents