6.3.7.5

Supported services and objects

BIBBs used by the converter

The BIBBs (BIBB: BACnet Interoperability Building Block) are a collection of one or several
BACnet services. BACnet services are subdivided into A and B devices. An A device operates
as client and a B device as server.
The converter is a server and therefore operates as B device, as "BACnet Application Specific
Controller" (B-ASC).
It uses the following executed BIBBs.

Overview of the BIBB used and the associated services

Short designation
DS-RP-B
DS-RPM-B
DS-WP-B
DM-DDB-B
DM-DOB-B
DM-DCC-B
DS-COV-B
The converter can simultaneously process up to 32 SubscribeCOV services. These can all
refer to the same object instances - or different object instances.
SubscribeCOV monitors the property changes of the following objects:
● Analog Input AI...
● Analog Output AO...
● Analog Value AV...
● Binary Value BV...
● Multi-State Input MSI...
Note
SubscribeCOV services are not retentive; i.e. the master must re-initiate the SubscribeCOV
services when restarting the converter.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
BIBB
Data Sharing-ReadProperty-B
Data Sharing-ReadMultipleProperty-B
Data Sharing-WriteProperty-B
Device Management-Dynamic Device
Binding-B
Device Management-Dynamic Object
Binding-B
Device Management-DeviceCommuni‐
cationControl-B
Data Sharing-COV-B
Advanced commissioning
6.3 Drive control
Service
ReadProperty
ReadPropertyMultiple
WriteProperty
● Who-Is
● I-Am
● Who-Has
● I-Have
DeviceCommunicationControl
● SubscribeCOV,
● ConfirmedCOVNotification,
● UnConfirmedCOVNotification