Interconnection Of The Receive Data; Extending The Telegram - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Figure 6-16
The converter saves the receive data as follows:
● "Word" format in r2050
● "Double word" format in r2060
● Bit-by-bit in r2090 ...r2093)

Extending the telegram

Extend the telegram by "attaching" additional signals.
Interconnect additional PZD send words and PZD receive words with signals of your choice via
parameters r2050 and p2051.
Freely interconnecting signals in the telegram
Interconnect additional PZD send words and PZD receive words with signals of your choice via
parameters r2050 and p2051.
Parameter
Number
p0922
r2050[0...11]
p2051[0...16]
r2053[0...16]
r2060[0...10]
p2061[0...15]
r2063[0...15]
p2079
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC

Interconnection of the receive data

Name
PROFIdrive PZD telegram selection
CO: PROFIdrive PZD receive word
CI: PROFIdrive PZD send word
PROFIdrive diagnostics send PZD word
CO: PROFIdrive PZD receive double word
CI: PROFIdrive PZD send double word
PROFIdrive diagnostics PZD send double word
PROFIdrive PZD telegram selection extended
Advanced commissioning
6.3 Drive control
Factory setting
1
-
0 or dependent on
the converter
-
-
0
-
1
219