Motor Saturation Characteristic Flux 3 / Mot Saturat.flux 3; Motor Saturation Characteristic Flux 4 / Mot Saturat.flux 4; Motor Saturation Characteristic I_Mag 1 / Mot Sat. I_Mag 1 - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
See also: p0367
Note
For induction motors, p0363 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0364[0...n]

Motor saturation characteristic flux 3 / Mot saturat.flux 3

Access level: 4
Can be changed: T, U
Unit group: -
Min:
10.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 3rd value pair of the characteristic.
Sets the third flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
See also: p0368
Note
For induction motors, p0364 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0365[0...n]

Motor saturation characteristic flux 4 / Mot saturat.flux 4

Access level: 4
Can be changed: T, U
Unit group: -
Min:
10.0 [%]
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 4th value pair of the characteristic.
Sets the fourth flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
See also: p0369
Note
For induction motors, p0365 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0366[0...n]

Motor saturation characteristic I_mag 1 / Mot sat. I_mag 1

Access level: 4
Can be changed: T, U
Unit group: -
Min:
5.0 [%]
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
800.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
800.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
800.0 [%]
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: 6723, 6838
Factory setting:
115.0 [%]
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: 6723, 6838
Factory setting:
125.0 [%]
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: 6723, 6838
Factory setting:
50.0 [%]
531