Bypass Dead Time / Bypass T_Dead; Debypass Delay Time / Debypass T_Del; Bypass Delay Time / Bypass T_Del - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
Description:
Control and feedback signals of the bypass switch.
Bit field:
Bit
00
01
05
06
07
10
11
Dependency:
The "Bypass" function is only available for induction motors.
Note
Control bits 0 and 1 should be interconnected to the signal outputs via which the switches in the motor feeder cables
should be controlled. These should be selected/dimensioned for switching under load.
p1262[0...n]

Bypass dead time / Bypass t_dead

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the dead time for non-synchronized bypass.
Dependency:
The "Bypass" function is only available for induction motors.
Note
This parameter is used to define the changeover time of the contactors. It should not be shorter than the de-magnetizing
time of the motor (p0347).
The total changeover time for the bypass is based on the total of p1262 plus the OFF time for the relevant switch
(p1274[x]).
p1263

Debypass delay time / Debypass t_del

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the delay time to switch back to converter operation for a non-synchronized bypass.
Dependency:
The "Bypass" function is only available for induction motors.
p1264

Bypass delay time / Bypass t_del

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the delay time for switching to line operation for a non-synchronized bypass.
Dependency:
The "Bypass" function is only available for induction motors.
660
Signal name
Command switch motor - power unit
Command switch motor - line supply
Feedback signal switch motor - power unit
Feedback signal switch motor - line supply
Bypass command (from p1266)
Bypass in process sequence
Bypass enabled
1 signal
Close
Close
Closed
Closed
Yes
Yes
Yes
Calculated: CALC_MOD_REG Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
20.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
300.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
300.000 [s]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
0 signal
FP
Open
-
Open
-
Opened
-
Opened
-
No
-
No
-
No
-
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
1.000 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
1.000 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
1.000 [s]
SINAMICS G120X converter