Parameters
7.2 Parameter list
r1593[0...1]
CO: Field weakening controller / flux controller output / Field/Fl_ctrl outp
Access level: 4
Can be changed: -
Unit group: 6_2
Min:
- [Arms]
Description:
Display and connector output for the output of the field weakening controller (synchronous motor).
Index:
[0] = PI output
[1] = I output
p1595[0...n]
Field weakening controller additional setpoint / Field_ctr add_setp
Access level: 4
Can be changed: T, U
Unit group: -
Min:
-80.00 [%]
Description:
Sets an additional setpoint for the field weakening controller.
The value refers to the dynamic voltage reserve (p1574).
Note
For a value equal to zero, the field weakening controller is activated when the maximum voltage, calculated with the
average value of the DC link voltage, is reached.
Negative values cause the field weakening controller to intervene earlier, so that the voltage can move away from the
modulation depth limit.
p1596[0...n]

Field weakening controller integral-action time / Field_ctrl Tn

Access level: 3
Can be changed: T, U
Unit group: -
Min:
10 [ms]
Description:
Sets the integral-action time of the field-weakening controller.
r1597

CO: Field weakening controller output / Field_ctrl outp

Access level: 4
Can be changed: -
Unit group: -
Min:
- [%]
Description:
Displays the output of the field weakening controller.
The value is referred to the rated motor flux.
r1598
CO: Total flux setpoint / Flux setp total
Access level: 3
Can be changed: -
Unit group: -
Min:
- [%]
696
Calculated: -
Scaling: p2002
Unit selection: p0505
Max:
- [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max:
50.00 [%]
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
10000 [ms]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6724
Factory setting:
- [Arms]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6726
Factory setting:
0.00 [%]
Dynamic index: DDS, p0180
Function diagram: 6723, 6724
Factory setting:
300 [ms]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6723
Factory setting:
- [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6714, 6723,
6724, 6725, 6726
Factory setting:
- [%]