6.7.2.3
U/f control with Standard Drive Control
Overview
Figure 6-73
Selecting application class Standard Drive Control in the quick commissioning adapts the
structure and the setting options of the U/f control as follows:
● Starting current closed-loop control: At low speeds, a controlled motor current reduces the
tendency of the motor to oscillate.
● With increasing speed, the converter changes from closed-loop starting current control to U/
f control with load-dependent voltage boost.
● The slip compensation is activated.
● Soft starting is not possible.
● Reduced setting options
Function description
Characteristics after selecting the application class Standard Drive Control
①
②
Figure 6-74
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Default setting of the U/f control after selecting Standard Drive Control
The closed-loop starting current control optimizes the speed control at low speeds
The converter compensates the voltage drop across the motor stator resistance
Characteristics after selecting Standard Drive Control