Rtc Dtc3 Weekday Of Activation / Rtc Dtc3 Day Act; Rtc Dtc3 Switch-On Time / Rtc Dtc3 T_On - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

00
01
Dependency:
See also: p8409, p8420, p8421, p8422
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8430[0...6]

RTC DTC3 weekday of activation / RTC DTC3 day act

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the weekday on which timer 3 is activated (DTC3).
The switch-on/off time is set in p8431/p8432 and the result displayed via binector output r8433.
Value:
0:
1:
Index:
[0] = Monday
[1] = Tuesday
[2] = Wednesday
[3] = Thursday
[4] = Friday
[5] = Saturday
[6] = Sunday
Dependency:
See also: p8409, p8431, p8432, r8433
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8431[0...1]

RTC DTC3 switch-on time / RTC DTC3 t_ON

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the switch on time in hours and minutes for timer 3 (DTC3).
BO: r8433 = 1 signal:
The condition for the set weekday (p8430) and switch-on time has been fulfilled.
Index:
[0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency:
See also: p8409, p8430, r8433
NOTICE
This parameter can only be changed when p8409 = 0.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Timer on
Timer ON negated
Weekday deactivated
Weekday activated
Yes
No
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: -
Unit selection: -
Max:
59
Parameters
7.2 Parameter list
No
-
Yes
-
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
0