Preparing For Commissioning; Collecting Motor Data - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

5.3

Preparing for commissioning

5.3.1

Collecting motor data

Data for a standard induction motor
Before starting commissioning, you must know the following data:
● Which motor is connected to the converter?
Note down the Article No. of the motor and the motor's nameplate data.
If available, note down the motor code on the motor's nameplate.
Figure 5-1
● In which region of the world is the motor to be used?
- Europe IEC: 50 Hz [kW]
- North America NEMA: 60 Hz [hp] or 60 Hz [kW]
● How is the motor connected?
Pay attention to the connection of the motor (star connection [Y] or delta connection [Δ]).
Note the appropriate motor data for connecting.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Example of the rating plate for a standard induction motor
Commissioning
5.3 Preparing for commissioning
153