Advanced commissioning
6.3 Drive control
6.3.2.4

Analog inputs

Function description
1)

Define the analog input type

The parameter p0756[x] and the switch on the converter specify the analog input type.
Table 6-4
AI 0 Unipolar voltage input
AI 1 Unipolar voltage input
AI 2 Unipolar current input (factory setting)
AI 3 LG-Ni1000 temperature sensor
196
with I/O Extension Module

Default settings via parameter p0756

Unipolar voltage input monitored
Unipolar current input
Unipolar current input monitored
Bipolar voltage input (factory setting)
Unipolar voltage input monitored
Unipolar current input
Unipolar current input monitored
Bipolar voltage input (factory setting)
Unipolar current input monitored
LG-Ni1000 temperature sensor
Pt1000 temperature sensor
No sensor connected
DIN-Ni1000 temperature sensor (6180 ppm / K)
Pt1000 temperature sensor
No sensor connected (factory setting)
DIN-Ni1000 temperature sensor (6180 ppm / K)
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
‑10 V ... +10 V
0 V ... +10 V
+2 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
‑10 V ... +10 V
0 mA ... +20 mA
+4 mA ... +20 mA
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
p0756[0] = 0
1
2
3
4
p0756[1] = 0
1
2
3
4
p0756[2] = 2
3
6
7
8
10
p0756[3] = 6
7
8
10
SINAMICS G120X converter