Parameters
7.2 Parameter list
p1530[0...n]

Power limit motoring / P_max mot

Access level: 2
Can be changed: T, U
Unit group: 14_5
Min:
0.00 [kW]
Description:
Sets the power limit when motoring.
Dependency:
See also: p0500, p1531
Note
The power limit is limited to 300% of the rated motor power.
p1531[0...n]

Power limit regenerative / P_max gen

Access level: 2
Can be changed: T, U
Unit group: 14_5
Min:
-100000.00 [kW]
Description:
Sets the regenerative power limit.
Dependency:
See also: r0206, p0500, p1530
Note
The power limit is limited to 300% of the rated motor power.
For power units without energy recovery capability, the regenerative power limit is preset to 30 % of the power r0206[0].
For a braking resistor connected to the DC link (p0219 > 0), the power limit when generating is automatically adapted.
For power units with energy recovery, the parameter is limited to the negative value of r0206[2].
r1533

Current limit torque-generating total / Iq_max total

Access level: 3
Can be changed: -
Unit group: 6_2
Min:
- [Arms]
Description:
Displays the maximum torque/force generating current as a result if all current limits.
r1536[0...1]

Current limit maximum torque-generating current / Isq_max

Access level: 4
Can be changed: -
Unit group: 6_2
Min:
- [Arms]
Description:
Displays the maximum limit for the torque-generating current component.
Index 0 indicates the signal limited by the Vdc controller.
Index:
[0] = Limited
[1] = Unlimited
688
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: p0505
Max:
100000.00 [kW]
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: p0505
Max:
-0.01 [kW]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max:
- [Arms]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max:
- [Arms]
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6640
Factory setting:
0.00 [kW]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6640
Factory setting:
-0.01 [kW]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6640
Factory setting:
- [Arms]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6640, 6710
Factory setting:
- [Arms]