r0021
CO: Actual speed smoothed / Actual speed
Access level: 2
Can be changed: -
Unit group: 3_1
Min:
- [rpm]
Description:
Displays the calculated and smoothed rotor speed.
Frequency components from the slip compensation (for induction motors) are not included.
Dependency:
See also: r0022, r0063
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
r0022
Actual speed rpm smoothed / Actual speed
Access level: 3
Can be changed: -
Unit group: -
Min:
- [rpm]
Description:
Displays the calculated and smoothed rotor speed.
Frequency components from the slip compensation (for induction motors) are not included.
r0022 is identical to r0021, however, it always has units of rpm and contrary to r0021 cannot be changed over.
Dependency:
See also: r0021, r0063
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
r0024
Output frequency smoothed / Output frequency
Access level: 3
Can be changed: -
Unit group: -
Min:
- [Hz]
Description:
Displays the smoothed output frequency.
Frequency components from the slip compensation (for induction motors) are included.
Dependency:
See also: r0066
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output frequency is available smoothed (r0024) and unsmoothed (r0066).
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
- [rpm]
Calculated: -
Scaling: p2000
Unit selection: -
Max:
- [rpm]
Calculated: -
Scaling: p2000
Unit selection: -
Max:
- [Hz]
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6799
Factory setting:
- [rpm]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6799
Factory setting:
- [rpm]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6300, 6799
Factory setting:
- [Hz]
473