Note
DO: Digital Output
X204: IO module terminal
Relay output: NO = normally open, NC = normally closed
Inversion using p0748 has been taken into account.
p0748

CU invert digital outputs / CU DO inv

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Setting to invert the signals at the digital outputs.
Bit field:
Bit
00
01
02
03
04
05
Note
DO: Digital Output
X204: IO module terminal
Relay output: NO = normally open, NC = normally closed
r0751.0...11

BO: CU analog inputs status word / CU AI status word

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and binector output for the status of the analog inputs.
Bit field:
Bit
00
01
02
03
08
09
10
11
Note
AI: Analog Input
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Signal name
DO 0 (NO: X134. 19 / NC: X134. 18)
DO 1 (NO: X134. 24 / NC: X134. 23)
DO 2 (NO: X204. 98 / NC: X204. 99)
DO 3 (NO: X204. 95 / NC: X204. 96)
DO 4 (NO: X204. 93)
DO 5 (NO: X204. 91)
Signal name
Analog input AI0 wire breakage
Analog input AI1 wire breakage
Analog input AI2 wire breakage
Analog input AI3 wire breakage
Analog input AI0 no wire breakage
Analog input AI1 no wire breakage
Analog input AI2 no wire breakage
Analog input AI3 no wire breakage
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
7.2 Parameter list
Data type: Unsigned32
Dynamic index: -
Function diagram: 2201, 2242
Factory setting:
0000 0000 bin
0 signal
FP
Not inverted
-
Not inverted
-
Not inverted
-
Not inverted
-
Not inverted
-
Not inverted
-
Data type: Unsigned16
Dynamic index: -
Function diagram: 2251, 2252
Factory setting:
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
565