Environmental requirements

Condition
Operational
Ambient
0°C to 40°C (32°F to 104°F)
temperature
Relative
5% to 93% at 40°C (104°F) with
humidity
maximum gradient of 10% per
(non-condensing)
hour
Altitude (above
0 to 3000 m (10,000 feet)
sea level
Shock
10 G, 11 ms, half-sine wave
Vibration
Random vibration is 5-10Hz @
+5db/Oct; 10-200Hz @
0.0005Grms; 200-500Hz @
-5db/Oct. Scale 0.05 Grms
Air flow
SAN512B-6 Maximum: 1711 cmh
(1007 cfm)
SAN512B-6 Nominal: ~985 cmh
(~580 cfm)
SAN256B-6 Maximum: 953 cmh
(561 cfm)
SAN256B-6 Nominal: ~ 486 cmh
(~286 cfm)
Heat dissipation
SAN256B-6 - refer to Watts and
Btu/hr values under VAC inputs
in Typical, Idle, and Maximum
Power Consumption tables.
SAN512B-6- refer to Watts and
Btu/hr values under VAC inputs
in Typical, Idle, and Maximum
Power Consumption tables.
Operating noise
SAN256B-6: 64.2 dB
SAN512B-6: 68.2 dB
Power supply requirements
The minimum number of power supplies needed in your system for operation and
to achieve redundancy depends on the blade and port configuration and the AC
input voltage level. N is minimum number of power supplies to operate
configuration, N+N doubles power supplies for full AC input and DC output
redundancy, and N+1 adds additional power supply for DC output redundancy in
case of single power supply failure. Although examples for different port and
blade configurations are provided, for more information and help with
determining the actual number of power supplies for your deployment, contact
your local representative.
Non-operational (storage)
-25°C to 70°C (-13°F to 158°F)
10% to 93% at 70°C (158°F)
0 to 12000 m (40,000 feet)
20 G, 11 ms, half-sine wave
Random Vibration is 3-10Hz @
+5db/Oct; 10-200Hz @
0.0065Grms; 200-500Hz @
-5db/Oct. Scale 1.12 Grms
N/A
N/A
N/A