For information about LED patterns, refer to Chapter 6, "Monitoring the
switch," on page 69.
14. Ground the chassis by attaching a ground wire from facilities ground to an
appropriate crimp connector and attaching the connector to the 2AWG
Panduit LCD2-14AF lug located to the left of the bottom fan assembly near
the bottom of the chassis.
Using HVAC/HVDC power cords
HVAC/HVDC power supply power cords, available from Brocade, are shipped
with an Anderson Saf-D-Grid
unterminated 14 AWG UL 600V 90C wires with ring lugs on the power source end.
Power cord length is 6 m (19 ft. 8 in.). For connecting to a power source, attach
either an AC power plug to these wires that meets your facility and local code
requirements, or connect these wires to appropriate DC power terminal blocks.
The following table defines the function of the 14 AWG wires in the power cable:
Table 7. HVAC/HVDC power cable
Wire label
Color
L+
Brown
Blue
PE
Green with yellow stripe
The Anderson Saf-D-Grid
keyed so that it only fits one way into the power supply. Note that the connector's
latch should be positioned under the connector and will latch when the power
cord connector is fully inserted into the power supply.
®
400 connector on the power supply end and three
Function
Return positive (+)
Negative (-)
Earth ground (PE)
®
connector on the power supply end of the cord is
Chapter 4. Initial Setup and Verification