IBM SAN512B-6 Installation, Service And User Manual page 268

Ibm storage networking
Table of Contents

Advertisement

Power consumption (idle configuration)
No optics or connections, ports disabled, and system completed boot up, fans at
low speed.
244
SAN512B-6 Installation, Service, and User Guide
@100 VAC
Model name
input
SAN256B-6
840 W
2867 BTU/hr
SAN512B-6
1515 W
5171 BTU/hr
@200 VAC
@-48 VDC
input
input
822 W
Not
supported
2806 BTU/hr
1481 W
Not
supported
5055 BTU/hr
Minimum
number of
power
supplies
Notes
2 power
SAN256B-6
supplies for
fully loaded:
AC low line
2 CP blades,
(100–120
2 CR blades,
VAC)
4 FC32-48
port blades, 2
1 power
fan
supply for
assemblies
AC high line
(200–240
VAC)
Device ships
with 2 power
supplies. One
provides
system
power, but
both must be
installed to
provide
power
efficiency and
redundancy.
3 power
SAN512B-6
supplies for
fully loaded:
AC low line
2 CP blades,
(100–120
2 CR blades,
VAC)
8 FC32-48
blades, 3 fan
2 power
assemblies
supplies for
AC high line
(200–240
VAC)
Device ships
with 3 or 4
power
supplies. Two
provide
system
power, but 3
or 4 must be
installed to
provide
power
efficiency and
redundancy.