Zone Setup (continued)

Setting Load Types

Fixture load type
Incandescent
MLV (magnetic low-voltage)
ELV (electronic low-voltage)
Hi-Lume
/Eco-10
®
Non-dim load type
Neon/Cold cathode
Tu-Wire
®
DMX
RGB/CMY DMX
Zone ratings:
• Not all zones must be connected; however, connected zones must have a minimum load:
120 - 127 V
: 25 W; 220 - 240 V
• Maximum zone loads:
120 - 127 V
: 800 W; 220 - 240 V
• Maximum total lighting load for a magnetic low-voltage (MLV) varies by input voltage:
120 - 127 V
: 800 VA / 600 W; 220 - 240 V
®
Direct control via
GRAFIK Eye
LUTRON
Choose this load type from the menu
Incandescent
LUTRON
MLV
®
Neon, CC
Tu-Wire
®
DMX
RGB/CMY DMX
: 40 W
: 1200 W
: 1200 VA / 960 W
Control via
QS
power module
®
on the GRAFIK Eye
QS:
®
Power module
Power module
Power module
Fluorescent module
Non-dim
Neon, CC
Tu-Wire
®
Load Type Notes
• All electronic low-voltage
(ELV) lighting used with an
interface must be rated for reverse
phase control dimming. Before
installing an ELV light source,
Power
LUTRON
verify with the manufacturer that
module
their transformer can be dimmed.
When dimming, an ELV interface
(such as the PHPM-PA-DV-WH)
LUTRON
must be used with the control
unit.
• For all DMX or RGB/CMY DMX
lighting, an external DMX interface
(such as the QSE-CI-DMX) must
be used with the control unit.