Setting Load Types - Lutron Electronics QSGRK-3PCE Quick Installation And Operation Manual

Grafik eye qs series
Hide thumbs Also See for QSGRK-3PCE:
Table of Contents

Advertisement

Zone Setup (continued)

Setting Load Types

Fixture load type
Incandescent
MLV (magnetic low-voltage)
ELV (electronic low-voltage)
Hi-lume
/Eco-10
®
®
0-10 V
Non-dim lighting loads
Neon/Cold cathode
DMX
RGB/CMY DMX
®
Direct control via
GRAFIK Eye
QS
®
control unit
LUTRON
Choose this load type from the menu
on the GRAFIK Eye
Incandescent
LUTRON
MLV
Non-dim
Neon, CC
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye
Control via
power module or
interface
Power
module or
LUTRON
interface
LUTRON
QS control unit:
®
Power module
Power module
Power module
Fluorescent module
Fluorescent module
Non-dim
Neon, CC
DMX
RGB/CMY DMX
QS Control Unit Quick Installation and Operation Guide 13
®
Load Type Notes
• All electronic low-voltage
(ELV) lighting used with an
interface must be rated for reverse
phase control dimming. Before
installing an ELV light source,
verify with the manufacturer that
their transformer can be dimmed.
When dimming, an ELV interface
(such as the NGRX-ELVI-CE-WH)
must be used with the control
unit.
• For all DMX or RGB/CMY DMX
lighting, an external DMX interface
(such as the QSE-CI-DMX) must
be used with the control unit.
Zone ratings:
• Not all zones must be connected;
however, connected zones must
have a minimum load of 40 W.
• Maximum loads:
10 A per unit
500 W per zone.
• Maximum total lighting load for a
magnetic low-voltage (MLV) load
is 500 VA / 400 W.

Advertisement

Table of Contents
loading

Table of Contents