Occupancy Sensor Setup

Configure Occupancy Sensor Settings

1. Enter programming mode (see page 15).
Main menu
2. Use the Master buttons to highlight "Sensor Setup" and press
Zone Setup
the OK button to accept.
Sensor Setup
3. Use the Master buttons to highlight "Occupancy" and press
the OK button to accept.
4. Use the Master buttons to highlight "Settings" and press the
Sensor Setup
OK button to accept.
5. Use the Master buttons to highlight the setting you wish to
Daylight
configure. See below for descriptions of the settings and their
Occupancy
values. Press the OK button to accept.
6. Use the Master buttons to adjust the value of the selected
setting. Press the OK button to accept.
Occ Sensor
7. The info screen will confirm that your setting has been saved.
8. Exit programming mode (see page 15).
Settings
Diagnostics
Occupancy Sensor Settings
Note: These settings affect all sensors assigned to the GRAFIK 
Eye QS.
Settings
Grace Period: If an occupancy sensor detects vacancy, motion
detected within the grace period will maintain the lights at the
Auto Turnoff
previously occupied level.
Turnoff Cancel
Range: 15 – 30 seconds (default 15 seconds).
Vacancy Delay: An additional time delay after vacancy is
detected and before unoccupied action occurs. Useful when
Auto Turnoff
occupancy sensor does not provide sufficient delay. Applies
only to occupancy sensors, not vacancy sensors.
5 minutes
Range: 0 – 30 minutes (default 0 minutes).
Auto Turnoff: If lights assigned to an occupancy sensor are
turned on manually without the sensor reporting occupancy,
the GRAFIK Eye QS can be set to automatically turn off the
lights after a set time delay. Disable this feature by setting the
time delay to 0 (disabled).
Saved
Saved
Range: 1 – 30 minutes (default 30 minutes).
Zone Fade: When in Zone Mode, lights can be set to fade to
the unoccupied levels over this period of time.
Range: 0 – 59 seconds; 1 – 60 minutes (default 10 seconds).
®