Step 9: Assign Load Types - Lutron Electronics Grafik Eye GRX-4000 Series Installer's Manual

Installing, operating and maintaining with xp series switching panels
Hide thumbs Also See for Grafik Eye GRX-4000 Series:
Table of Contents

Advertisement

Assign Load Types

STEP 9: Assign Load Types

Assigning Load Types is done using the Circuit
Selector located in each XP Series panel.
Press button 5 repeatedly until
Use buttons 1 and 2 to view present load type of each
circuit. Note that ' - ' in the Value display means a
Load Type is not assigned to the circuit.
If load types are already assigned, compare them to
the Circuit Directory (if provided).
If there are no changes to be made, skip to Step 10.
To change Load Types:
A. Press and hold buttons 1 and 5 until
LED lights.
B. Press button 5 repeatedly until
C. Tap button 2 so that 'AC' (All Circuits) appears in
the Circuit display.
D. Press button 3 repeatedly (press button once per
second since updating is slower in all circuits) until
'4' appears in the Value display.
E. Press and hold buttons 1 and 5 until
V
V
LED lights.
IEW
ALUE
Notes:
• Most applications will use Load Type 4. Use Load
Type 6 for circuits controlling screens.
• The Circuit Selector Display will go out automatically
after 20 minutes of the last button press.
• Mark all changes to the Circuit Selector's Values on
the Circuit Directory for future reference.
?
For More Information...
Circuit Selector Functions.................23
Circuit Directory.................................26
10
Step by Step instructions for GRAFIK Eye
Load Type lights.
S
V
ELECT
ALUE
Load Type lights.
Switching Panel
Circuit Selector
Link Status
Power OK (Pins 1,2)
Data OK (Pins 3,4)
S
C
ELECT
IRCUIT
1
2
Circuit
V
V
IEW
ALUE
S
V
ELECT
ALUE
3
4
Value
S
V
D
ELECT
ALUE
ISPLAYED
5
Load Type
1 Inc/Mag LV
4 Non-dim
2 Fluorescent
5 Elec. LV
3 Neon/CC
– Unassigned
Control and Zone Assigned
Using circuit schedule
Using Zone Capture
TM
Power OK (Pins 1,2)
Link Status
Low End Trim (optional)
Data OK (Pins 3,4)
High End Trim (optional)
S
C
ELECT
IRCUIT
Circuit Level
1
®
2
Circuit
V
V
IEW
ALUE
S
V
ELECT
ALUE
3
4 4 4 4 4
4
Value
S
V
D
ELECT
ALUE
ISPLAYED
5
Load Type
1 Inc/Mag LV
4 Non-dim
2 Fluorescent
5 Elec. LV
3 Neon/CC
– Unassigned
Control and Zone Assigned
Using circuit schedule
Using Zone Capture
TM
Low End Trim (optional)
High End Trim (optional)
Circuit Level
®
A,F

Hide quick links:

Advertisement

Table of Contents
loading