Associating Multiple Grafik Eye; Control Units - Lutron Electronics GRAFIK Eye QSGRJ-3P Installation And Operation Manual

Grafik eye qs control unit
Hide thumbs Also See for GRAFIK Eye QSGRJ-3P:
Table of Contents

Advertisement

Associating Multiple GRAFIK Eye

When there is more than one GRAFIK 
Eye QS control unit in a system, it is
often convenient to associate them so
that certain functions carry over to other
associated GRAFIK Eye QS control units.
• Wired units: When first wired on the QS
link, all unprogrammed GRAFIK Eye QS
wired control units will replicate scene
activations and Master button presses by
other control units on the link. Associating
or disassociating control units determines
which units on the QS link will "talk"
or "listen" to each other. Control units
associated on a wired QS link will also
replicate timeclock and contact closure
settings.
• Wireless units: GRAFIK Eye QS Wireless
control units will not automatically
replicate scene activations or
Master button presses, and must be
programmed to do so. (Associating
two wireless control units will not pass
timeclock and contact closure settings to
each other.) When associating multiple
wireless control units, make sure the
wireless mode of both units is set to
"Enabled."
Note: The wireless signal has a range
of 30 feet (10 m) through standard
construction.
®
QS Control Units
®
To associate two GRAFIK Eye QS

control units:

1. Begin with the GRAFIK Eye QS control
unit that will "talk" (button presses will be
replicated on the other control unit; in the
drawing below this is GRAFIK Eye QS A).
Press and hold the top and bottom scene
buttons until the LEDs flash (about
3 seconds).
2. Continue with the GRAFIK Eye QS control
unit that will "listen" (replicate button
1
presses on the other control unit; in the
drawing below this is GRAFIK Eye QS B).
Press and hold the top scene button until
the LEDs flash (about 3 seconds).
3. Return to the GRAFIK Eye QS control unit
that will "talk" (A). Press and hold the top
and bottom scene buttons until the LEDs
stop flashing (about 3 seconds).
4. Repeating the process in reverse allows
GRAFIK Eye QS A to also "listen" to
GRAFIK Eye QS B, so that both units will
follow each other.
To disassociate two GRAFIK Eye QS
control units:
Simply repeat the association steps,
in the same order; press and hold
the bottom scene button on B to
disassociate.
Note: A control unit can be associated
with as many other control units as exist
on the link. Any unit can replicate any
other unit's button presses, and any
unit's button presses can be replicated
on an unlimited number of control units.
1
2
3
4
5
6
2
3
4
5
6
On the unit that will "listen", press and hold the
top scene button for 3 seconds to associate,
or press and hold the bottom scene button for
3 seconds to disassociate with the unit that will
"talk".
1
2
3
4
5
GRAFIK Eye QS A
"Talks" to GRAFIK 
Eye QS B; scene
activation and
Master button
presses activated on
unit A are replicated
on unit B.
GRAFIK Eye
QS Installation and Operation Guide 49
®
OK
On the unit that will "talk", press
and hold the top and bottom
scene buttons for 3 seconds
to begin or end association or
disassociation with the unit that
will "listen".
OK
Associate
OR
Disassociate
6
1
2
3
4
5
OK
GRAFIK Eye QS B
"Listens" to GRAFIK 
Eye QS A; unit B
replicates scene
activations and
Master button
presses on unit A.
6
OK

Advertisement

Table of Contents
loading