Overview Of Pelv (Class 2: Usa) Wiring - Lutron Electronics GRAFIK Eye QSGRJ-3P Installation And Operation Manual

Grafik eye qs control unit
Hide thumbs Also See for GRAFIK Eye QSGRJ-3P:
Table of Contents

Advertisement

Wiring the GRAFIK Eye

Overview of PELV (Class 2: USA) Wiring

IR Wiring
18 AWG (1.0 mm
)
2
each terminal
From external
IR connection
(by others)
Contact Closure Input Wiring
For settings, see page 21.
Example:
Occupancy sensor
(maximum 1)
Signal
+V Input
Circuit Common
LUT-ELI-3PH
Example:
Emergency lighting interface (maximum 1)
Note: The GRAFIK Eye QS control unit
must be powered by a Normal/Emergency
distribution panel for proper ELI operation.
Refer to the LUT-ELI-3PH Installation Guide
for the complete wiring diagram.
®
QS:
®
1: IR DATA
2: IR COM
A: CCI SIG
B: 24 V
C: CCI COM
Control Wiring
Common and power (terminals 1 and 2):
18 AWG
Two 18 AWG (1.0 mm
(1.0 mm
)
2
each
terminal
A: CCI SIG
B: 24 V
C: CCI COM
Data (terminals 3 and 4):
Twisted, shielded pair 22 AWG (0.5 mm
each terminal
) each terminal
2
To control stations,
shades, or other
GRAFIK Eye QS
control units
GRAFIK Eye
1 2 3 4 5 6 L N
1 2 3 4 5 6 L N
1 2 3 4 5 6 L N
1: COM
2: 24 V
*
* Do not connect terminal 2
3: MUX
between any GRAFIK Eye QS and
4: MUX
any other power supply, including
another GRAFIK Eye QS.
See page 9 for detailed wiring
example.
)
2
1 2 3 4 5 6 L N
Note: Use appropriate wire connecting devices
as specified by local codes.
QS Installation and Operation Guide 7
®
N H 1 2 3