System reliability guidelines

To help ensure proper system cooling and system reliability, make sure that the
following requirements are met:
v Each of the drive bays has a drive or a filler panel and electromagnetic
v If the server has redundant power, each of the power-supply bays has a power
v There is adequate space around the server to allow the server cooling system to
v You have followed the cabling instructions that come with optional adapters.
v You have replaced a failed fan within 48 hours.
v You have replaced a hot-swap drive within 2 minutes of removal.
v You do not operate the server without the air baffles installed. Operating the
Note: The air baffle comes with the microprocessor 2 expansion board option.
v Microprocessor socket 2 always contains either a socket cover or a
v You have installed the air baffle and fan 2 when you installed the

Working inside the server with the power on

Attention: Static electricity that is released to internal server components when
the server is powered-on might cause the server to halt, which might result in the
loss of data. To avoid this potential problem, always use an electrostatic-discharge
wrist strap or other grounding system when you work inside the server with the
power on.
The server supports hot-plug, hot-add, and hot-swap devices and is designed to
operate safely while it is turned on and the server cover is removed. Follow these
guidelines when you work inside a server that is turned on:
Note: In order to work inside the server with the power on, you have to disable
the power cut-off switch before removing the server cover.
v Avoid wearing loose-fitting clothing on your forearms. Button long-sleeved
v Do not allow your necktie or scarf to hang inside the server.
v Remove jewelry, such as bracelets, necklaces, rings, and loose-fitting wrist
v Remove items from your shirt pocket, such as pens and pencils, that could fall
v Avoid dropping any metallic objects, such as paper clips, hairpins, and screws,
38
System x3300 M4 Type 7382: Installation and Service Guide
compatibility (EMC) shield installed in it.
supply installed in it.
work properly. Leave approximately 50 mm (2.0 in.) of open space around the
front and rear of the server. Do not place objects in front of the fans. For proper
cooling and airflow, replace the server cover before you turn on the server.
Operating the server for extended periods of time (more than 30 minutes) with
the server cover removed might damage server components.
server without the air baffles might cause the microprocessor to overheat.
microprocessor and heat sink.
microprocessor 2 expansion board option.
shirts before working inside the server; do not wear cuff links while you are
working inside the server.
watches.
into the server as you lean over it.
into the server.