WARNING:
The UPS is fixed on the pallet with four balance brackets and four M12
screws. When taking apart the two balance brackets from the UPS, pay
attention to the movement of the casters to avoid accidents.
• The casters are designed to move on level ground. Do not move the UPS on an
uneven surface. This might cause damage to the casters or trip the UPS which
could damage the unit.
• After the UPS has been removed from the pallet to the ground, we suggest that at
least three people move the UPS to the installation area. With their two hands, one
person holds a lateral side of the UPS, another person holds the other lateral side
of the UPS, and the other person pushed the UPS, either from the front side or
from the backside, to move the unit to the installation area. This is the best way to
avoid tipping the UPS.
• If you need to move the UPS over a long distance, please use appropriate
equipment (e.g. forklift). Do not use the UPS casters to move the unit over a long
distance.
5.4
UPS Installation
NOTE:
Please use appropriate equipment (e.g. forklift) to move the UPS.
Please follow the steps below:
Step 1
Before installing the UPS in a designated installation area, please double-check
whether the area's floor weight loading is sufficient to bear the UPS, external battery
cabinet(s) and handling equipment (e.g. forklift) to avoid accidents.
Step 2
After the UPS is moved to the designated installation area, use a #17 wrench to
stabilize the UPS four leveling feet on the floor. Please note that the UPS must stand
on the floor stably and levelly without any tipping.
Step 3
Use eight M10 screws (four for the front, four for the rear) ❶ and four expansion M12
screws, washer plains and washer springs (two for the front, two for the rear) ❷ to fix
the UPS on the ground with four balance brackets. Please refer to
5-4
. The eight M10 screws and the four balance brackets are those been taken apart
from the UPS earlier while moving the UPS from the pallet to the ground (see
Transportation
). As for the four expansion nuts, they should be provided by qualified
service personnel.
Delta UPS DPH 50-200kVA
Figure 5-3
Figure
~
5.3 UPS
46