Step 4
Please log in as an Administrator. For the Administrator password, please contact
service personnel.
Step 5
Go to SETUP → Mode Setting → Frequency Conversion.
WARNING:
Once you select 'Frequency Conversion' mode, the UPS will run in Standby
mode and the output will be terminated.
Step 6
Tap the icon (
) to go back to the Main Screen and tap the ON/ OFF Button (
Delta UPS DPH 50-200kVA
Administrator Login
ON/ OFF
Button
).