Step 7
After the inverter turns on, the UPS will run in Frequency Conversion mode, the output
frequency will be the same as the setup value, the LCD screen will show as below, and
the tri-color LED indicator will illuminate green.
6.2.7

Green Mode Start-up Procedures

WARNING: 
Before turning on the UPS, please read
Warnings
been followed.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet's breaker (Q5).
Step 3
Switch ON the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
If the bypass input is within the normal range, the UPS will run in Bypass mode.
Step 4
Log in as an Administrator. For the Administrator password, please contact service
personnel.
thoroughly and ensure that the precautions and instructions have
6.1 Pre Start-up & Pre Turn-off
97

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Modulon DPH Series and is the answer not in the manual?