6.2.2
Battery Mode Start-up Procedures
WARNING:
Before turning on the UPS, please read
Warnings
been followed.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet's breaker (Q5).
Step 3
Switch ON the Output Switch (Q4).
Step 4
Press any of the BATT. START buttons on the Communication Interfaces (I) for one
second.
Step 5
Tap the ON/ OFF Button (
Step 6
After the inverter turns on, the UPS will run in Battery mode, the LCD screen will show
as below, and the tri-color LED indicator will illuminate yellow.
thoroughly and ensure that the precautions and instructions have
) on the LCD screen.