Step 5
Now, each power module performs DC BUS discharging and its LED indicator flashes
green. After discharging, each power module's LED indicator will be off.
Step 6
About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED
indicator will be off.
Step 7
Switch OFF every external battery cabinet's breaker (Q5).
6.3.8
Energy Recycle Mode Turn-off Procedures
WARNING:
Energy Recycle mode is only applicable to single input and single unit
application.
Step 1
Tap the ON/ OFF Button (
let the bypass AC source supply power. At the moment, if the bypass is abnormal,
there is a risk of output interruption.
Step 2
Please log in as an Administrator. For the Administrator password, please contact
service personnel.
Step 3
Go to SETUP → Mode Setting → On-Line.
Step 4
Switch OFF the Input Switch (Q1) and Bypass Switch (Q2).
Delta UPS DPH 50-200kVA
) to shut down the UPS's inverter. After that, the UPS will
106