Step 6
About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED
indicator will be off.
Step 7
Switch OFF every external battery cabinet's breaker (Q5).
6.3.7
Green Mode Turn-off Procedures
WARNING:
Before turning off the UPS, please read
Warnings
been followed.
Step 1
Tap the ON/ OFF Button (
let the bypass AC source supply power. At the moment, if the bypass is abnormal,
there is a risk of output interruption.
Step 2
Log in as an Administrator. For the Administrator password, please contact service
personnel.
Step 3
Go to SETUP → Mode Setting → On-Line.
Step 4
Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4). After
that, the UPS will run in Standby mode.
thoroughly and ensure that the precautions and instructions have
) to shut down the UPS's inverter. After that, the UPS will
6.1 Pre Start-up & Pre Turn-off
105