NOTE:
The recommended cable size is in accordance with
minimum requirements in
requirements:
70 ℃ copper wire
Ambient temperature is 30 ℃
If the ambient temperature exceeds 30 ° C, please refer to the IEC
standard to select a higher specification wire.
Table 5-2
battery Q'ty: 40 PCS and (3) default charge current for each power module
is 5A, default charge current for 200KW is 20A. The UPS has 5 power
module slots for redundancy. For other conditions different from
please contact Delta service personnel for relevant values.
Table 5-2: Specifications of Input/ Output/ Battery Cables, Switches & Breakers
UPS Capacity
Power Module Q'ty
Rated current at
220V with
battery charging
Recomm
ended
cable
size
Input
Maximu
m cable
size
Maximum cable
lug width
Screw size
Terminal type
Table B.52.2
is based on (1) default input/ output voltage: 220V, (2) default
DPH Series
50kVA/
50kW
25 mm
(L1/
×1 PC
L2/
(2 AWG
L3/N)
×1 PC)
240 mm
(L1/
×1 PC
L2/
(500
L3/N)
kcmil ×1
30 mm
(1.18")
*1
) and must meet the following
100kVA/
100kW
1
2
93A
186A
70 mm
2
2
×1 PC
(3/0 AWG
×1 PC)
240 mm
2
×1 PC
(500
kcmil ×1
PC)
PC)
30 mm
(1.18")
M10
M10
TLD10-70
IEC 60364-5-52
150kVA/
200kVA/
150kW
200kW
3
279A
50 mm
70 mm
2
×2 PCS
(1/0 AWG
(3/0AWG
×2 PCS)
×2 PCS)
240 mm
2
2
240 mm
×1 PC
(500
(500 kcmil
kcmil ×1
× 1 PC)
PC)
30 mm
30 mm
(1.18")
M10
(the
Table 5-2
,
4
372A
×2
2
PCS
×
2
1 PC
(1.18")
M10
49