7.6.9
Control
Path:
→ Control
Item
Buzzer
Reset Module
Reset System
Force Equalized
Charge
Force Bypass to
Inverter
7.6.10 Network Service
Path:
→ Network Service
Item
HTTP
HTTPS
Enable or disable the buzzer.
Reset the power modules or not.
In Bypass mode, when you tap the ON/ OFF Button (
start up the UPS but the UPS does not respond, please select
'Reset' to reset the power modules. After the power modules
are reset, please tap the ON/ OFF Button (
UPS.
Reset the system or not.
In Bypass mode, when you tap the ON/ OFF Button (
start up the UPS but the UPS does not respond, please select
'Reset' to reset the system. After the system is reset, please
tap the ON/ OFF Button (
Manually force the UPS to run in auto equalized charge mode
to charge the batteries.
Manually force the UPS to switch from bypass to inverter
when the inverter keeps staying in the soft-start status and is
unable to transfer to On-Line mode successfully.
Enable or disable HTTP service.
Enable or disable HTTPS service.
Description
) to start up the UPS.
Description
) to
) to start up the
) to