Step 2
Switch ON every external battery cabinet's breaker (Q5).
Step 3
Switch ON the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
If the bypass AC source is within the normal range, the UPS will transfer to run in
Bypass mode.
Step 4
Please log in as an Administrator. For the Administrator password, please contact
service personnel.
Step 5
Go to SETUP → Mode Setting → ECO.
Delta UPS DPH 50-200kVA
Administrator Login
ON/ OFF
Button
94