Tap the icon (
), and you can view the Internal Resistance Alarm Threshold.
Path:
→ BMS Setting (Administrator login required)
⚫
1.
Select 'CM' in the BMS Model list, you can view the Alarm Threshold Values (High
& Low)*
of Cell Voltage, String Voltage and Ambient Temperature.
1
You can also set up the following items. These settings must be carried out by
qualified service personnel. Please contact Delta customer service for assistance.
NOTE:
1. *
The Alarm Threshold Values (High & Low) are defined by the service
1
personnel during the installation process of the optional battery
management system (BMS).
Delta UPS DPH 50-200kVA
When the Cell IR. Value
Exceeds the Internal
Resistance Alarm
Threshold Value, the
Column Will Show the
Warning in Red.
Tap the Icon to View
the Internal Resistance
Alarm Threshold Value.