SECTION 3
Preparations for Communications
Trial Operation
Turn ON power.
Check operation of
external input terminal.
Test host device
communications online
Check communications
with the READ command.
Trial operation of the
system
END
During installation, use the Maintenance Mode to adequately check the environment and installation.
p. 66
RFID System
76
User's Manual
• Check that the supply voltage and the connection of power supply
terminals are correct.
• Check that the supply voltage to the I/O terminals is correct.
• Check that the RUN indicator on the Controller and the POWER indi-
cator on the Antenna are lit.
• Check stop operation using a reset input.
• Check the communications between the host device and Controller
with the TEST command.
• Check communications between Antennas and Tags with the READ
command.
• Check the whole system and I/O status while executing actual
commands.