Chapter 5 Function code
Function
Parameter
code
name
Hardware
P23.07
protection
configuration
Over-speed
P23.10
detection value
Over-speed
P23.11
detection time
Detection value
P23.12
of too large
speed deviation
Detection value
P23.13
of too large
speed deviation
Input phase
P23.14
loss detection
time
Output phase
P23.15
loss imbalance
detecting
Fault protection
P23.18
action selection
1
Fault protection
P23.19
action selection
2
VFD500 high performance vector control frequency inverter user manual
Description
Unit's digit: Wave-by-wave current limit enable
0: invalid; 1: valid
Ten's digit short to ground enable bit
0: invalid;
1: Valid power-on detection
2: Detection before operation
3: Check before power-on and operation
0.0%~120.0% maximum frequency
0.0s~30.0s0.:shielding
0.0%~100.0%(motor rated frequency)
0.0s~30.0s
0.0:shielding
0.0s~30.0s
0.0:forbidden
0%~100%
Unit's digit : input phase loss
0: coast to stop
1: Emergent stop
2: Stop as per stop mode
3: Continue to Run
Ten'unit: user self-defined fault 1
same as Unit's digit
Hundred'unit: user self-defined fault 2
same as Unit'digit
Thousand's unit: communication fault
same as unit's digit
Unit's digit: motor overload
0: Coast to stop
1: Emergent stop
2: Stop as per stop mode
3: Continue to run
Ten'unit: motor overheat
same as unit'digit
Hundred'unit: too large speed deviation
same as unit'digit
Thousand's unit: motor over speed
same as Unit'digit
- 92-
Default
Property
11
★
120.0%
☆
1.0s
☆
20.0%
☆
0.0s
☆
8.0s
☆
30%
☆
0000
☆
0000
☆