Veikong VFD500 Series User Manual page 131

High performance vector and torque control frequency inverter
Hide thumbs Also See for VFD500 Series:
Table of Contents

Advertisement

VFD500 high performance vector control frequency inverter user manual
Fault
Fault Name
code
Encoder
22
offline
Motor
25
over-speed
Too large
speed
26
deviation
Motor
auto-tuning
27
fault 1
Motor
auto-tuning
28
fault 3
Off load
31
EEPROM
read- write
32
fault
Running
33
time arrival
485Commu
nication
34
fault
Possible Causes
Display
1. Motor locked
Er.PGL
2. Encoder pulse setting wrong
3. Encoder offline
1: The encoder parameters are set
incorrectly.
Er. oS
2: The motor auto-tuning is not
performed.
3: The over-speed detection
parameters are set incorrectly
1: The encoder parameters are set
incorrectly.
2: The motor auto-tuning is not
Er.DEV
performed.
3: The detection parameters of too
large speed deviation are set
incorrectly.
1: The motor parameters are not
set
Er.tU1
according to the nameplate.
2: The motor auto-tuning times out.
1: The motor parameters are not
set
Er.tU3
according to the nameplate.
2: The motor auto-tuning times
out.
1、The frequency inverter running
Er. LL
current is lower than the setting
value.
1、 Eeprom Operate too frequent
Er.EEP
2、 The EEPROM chip is
damaged.
Er.TTA
Inverter trial time arrival
1, The work of the host computer is
not normal
Er.485
2, The communication line is not
normal
3, The communication parameter
set is incorrect
Chapter6 Fault diagnosis and solutions
1 check motor and mechanical
condition
2 set correct parameter for
encoder
3 check encoder connecting line
1: Set the encoder parameters
properly.
2: Perform the motor auto-tuning.
3: Set the over-speed detection
parameter correctly based on the
actual situation.
1: Set the encoder parameters
properly.
2: Perform the motor auto-tuning.
3: Set the detection parameters
correctly based on the actual
situation.
1: Set the motor parameters
according to the name plate
properly.
2: Check the cable connecting
between the Frequency inverter
and the motor.
1: Set the motor parameters
according to the name plate
properly.
2: Check the cable connecting
between the Frequency inverter
and themotor.
1、Confirm whether the load is
off
2、Check that the load is
disconnected or the parameter
setting is correct
1、 Operate Eeprom suitable
2、 Replace the main control
1:Contact agent or distributor
1. Check the connection of upper
computer
2. Check the communication
connection line
3. Set communication
parameters correctly
- 129-