Chapter 5 Function code
Function
Parameter name
code
Sleep mode and
P41.00
wake up selection
VFD500 high performance vector control frequency inverter user manual
41 Group Sleeping function
Description
Unit's digit: sleep mode selection
0:no sleep function
1:Sleep by frequency
2:AI1 sleep (AI1 as pressure
feedback)
3:AI2 sleep(AI2 as pressure feedback)
4:AI3 sleep (AI3 as pressure
feedback)
3:AI4 sleep(AI4 as pressure feedback)
Ten's digit :wake up mode selection
0:Wake up by frequency
1:AI1 wake up (AI1 as pressure
feedback)
2:AI2 wake up (AI2 as pressure
feedback)
3:AI3 wake up (AI3 as pressure
feedback)
4:AI4 wake up (AI4 as pressure
feedback)
Hundred's digit: Sleep wake direction
selection
0: positive direction
Sleep source (AI1 ~ AI4) > P41.03, inverter
will sleep
Wake-up source (AI1 ~ AI4) < P41.04, the
inverter will wake up
1: reverse direction
Sleep source (AI1 ~ AI4) < P41.03, inverter
sleep
Wake-up source (AI1 ~ AI4) > P41.04, the
inverter wakes up.
When the sleep source and wakeup source
are the same, please pay attention to the
size relationship of P41.03 and P41.04. If
the parameter setting is unreasonable,
when the wake-up condition is selected,
even if the sleep condition is established,
the sleep state cannot be entered, and
special attention is required when using.