Veikong VFD500 Series User Manual page 29

High performance vector and torque control frequency inverter
Hide thumbs Also See for VFD500 Series:
Table of Contents

Advertisement

VFD500 high performance vector control frequency inverter user manual
Table 3-20 VFD500 control circuit terminal instruction
Terminal
Type
Symbol
+10V
GND
Analog input
AI1
voltage
AI2
AO1
Analog
output
AO2
GND
+24V
Switch input
PLC
COM
DI1~DI4
HDI
Terminal
Name
10.10V±1%
Maximum output current:10mA,it provides power
Input voltage
supply to external potentiometer with resistance range
of:1KΩ~51KΩ
Analog
Internal isolation from COM
ground
Input voltage:0~10V:Impedance 22KΩ,Maximum
input voltage
Input current:0~20mA:Impedance 500Ω,Maximum
Analog input1
input current
Through the jumper switch AI1 0 ~ 10V and 0 ~ 20mA
analog input switch, the factory default voltage input.
Input voltage:0~10V:Impedance 22KΩ,Maximum
input voltage
Analog input
Input current:0~20mA:Impedance 500Ω,Maximum
2
input current
Through the jumper switch AI1 0 ~ 10V and 0 ~ 20mA
analog input switch, the factory default voltage input.
Output voltage:0~10V:Impedance ≥10KΩ
Output current:0~20mA:Impedance 200Ω~500Ω
Analog output
Through the jumper switch AO1 0 ~ 10V and 0 ~ 20mA
1
analog output switching, the factory default voltage
output.
Output voltage:0~10V:Impedance ≥10KΩ
Output current:0~20mA:Impedance 200Ω~500Ω
Analog output
Through the jumper switch AO1 0 ~ 10V and 0 ~ 20mA
2
analog output switching, the factory default voltage
output.
Analog
Internal isolation from COM
ground
24V±10%,Internal isolation from GND
Maximum output current:200mA
+24V current
To provide 24V power supply, generally used as a
digital input and output terminal power supply and
external sensor power
The factory default setting is connected PLC with
+24V
Digital input
Terminal for on-off input high and low level switch
terminal
When using the external signal to drive DI1~DI5, it
common
will disconnect the connector slip of PLC with the +24V
+24V ground
Internal isolation from GND
Optocoupler isolation, compatible with bipolar input
Digital input
Frequency range:0~200Hz
terminal 1~4
Voltage range:10V~30V
Digital input
Digital input terminal:same as DI1~DI4
- 27-
Chapter3 Product appearance and wiring
Terminal function description

Hide quick links:

Advertisement

Table of Contents
loading