VFD500 high performance vector control frequency inverter user manual Appendix B Profinet communication card usage
5.5 Configure the data characteristics of the slave
(1) Select Slave to switch to the device view
(2) Select the module under Modules on the right and double-click Add to Device
(3) Select the module in "Device overview" and set the function code of the PZD mapping
in "Properties" -> "Module Parameters" below.
Follow the image above
If the master wants to set function code P00.07, enter 7 in PZD3 (master->slave).
If the master wants to read the value of function code P27.06, enter 2706 in PZD3
(salve->master).
If the master wants to read the value of function code P27.10, enter 2710 in PZD4
(salve->master).
- 162-