Chapter 5 Function code
Function
Parameter name
code
Jump frequency 2
P01.16
upper limit
Jump frequency 3
P01.17
lower limit
Jump frequency 3
P01.18
upper limit
Risk speed or Jump frequency start up protection is used to some situation which need avoid motor speed
and speed range, for example, due to mechanical resonance ,P01.12 will be enabled to avoid risk speed in forward
or reverse mode .
Motor frequency
P01.18
P01.17
P01.16
P01.15
P01.14
P01.13
Multi-step speed
P01.19
reference source
VFD500 high performance vector control frequency inverter user manual
P01.15~maximum frequency(P01.06)
0.00Hz~(P01.18)
P01.17~maximum frequency(P01.06)
Giving frequency
Unit'digit:0 phase reference source
set by
0-multi-step speed(P01.21)
1-preset frequency (P00.07)
2:AI1
3:AI2
4:AI3(IO expansion board)
5:AI4(IO expansion board)
6:HDI pulse
7:Communication
8:PID
Ten's digit:Combination of multiple speed
0:Combination method
1:Priority method
- 43-
Description
Default
Property
0.00Hz
0.00Hz
0.00Hz
00