Chapter 5 Function code
Function
Parameter name
code
r05.09
AO2 actual value
AO2 output function
P05.10
signal selection
P05.11
AO2 output offset
P05.12
AO2 gain
The output error of AO2 can be corrected by P05.11 and P05.12, or the mapping relationship between signal
source and actual output can be changed. The formula is:
AO.c = P05.11 + P05.12 × AO.pAO.c: the actual output of AO2;
AO.p: AO2 value before correction and AO.c, AO.p, 100.0% of P05.11 corresponds to 10V or 20mA.
Example: Such as: AO2 is set to 4~20mA output:
1. Switch the corresponding AO2 jumper on the IO board to current
2. Set the function code: P05.11=20.0%, P05.12=0.80
r06.00
DI port status
DI1 Numeric input
P06.01
function
VFD500 high performance vector control frequency inverter user manual
Description
0.0%~100.0%
Same as P05.02 function description
-100.0%~100.0%
-10.00~10.00
06 Group Multi-function Digital input
Bit0~Bit8 Correspond to DI1~DI8
Bit12~Bit15 Correspond to VDI1~VDI4
0:No function
1:FORWARD
2:Reverse/Forward and reverse switchover
3:Three wire control
4:Forward jog command
5:Reverse jog command
6:Terminal UP
7:Terminal DOWN
8:Clear up UP/DOWN offset
9:Coast to stop/free stop
10:Fault reset
11:Reverse forbidden
12:Switching run command to Keypad
13:Switching run command to Communication
14:fast stop
15:external stop
16:Switch between motor 1 and motor 2
17:Pause operation
18:DC braking
19:Switch between torque and speed Control
20:Torque control disabled
21:Multi-step speed terminal 1
22:Multi-step speed terminal2
23:Multi-step speedterminal3
24:Multi-step speed terminal4
25:Frequency source switchover
26:Switch main frequency source to Numeric
frequency setting
27:Switch main frequency source to AI1
- 60-
Default
Property
-
0
0.0%
1.00
-