Chapter 5 Function code
Function
Parameter name
code
P44.34
Constant setting 1
P44.35
Constant setting 2
P44.36
Constant setting 3
P44.37
Constant setting 4
Constant setting 1 as
P44.38
per bit definition
Constant setting 2 as
P44.39
per bit definition
Constant setting 3 as
P44.40
per bit definition
Constant setting 4 as
P44.41
per bit definition
Constant setting for reference of variable selector or logic block input
r45.00
Counter 1 input value
r45.02
Counter 1 count value
P45.04
Counter 1 set value
Counter 1 maximum
P45.06
value
Counter 1
P45.08
Electronic gear
numerator
Counter 1
P45.09
Electronic gear
denominator
VFD500 high performance vector control frequency inverter user manual
Description
5: exclusive OR
6:Ref=1 effective;Ref2=1 ineffective
7:Ref1 up effective,Ref2 up ineffective
8:Ref1 up and signal reverse
9:Ref1 up and output 200ms pulse width
0~65535
0~65535
0~65535
-9999~9999
0~65535(define as bit)
0~65535(define as bit)
0~65535(define as bit)
0~65535(define as bit)
45 Group Multi-functional counter
The count value before the electronic gear,
that is, the number of pulses received by
the counter 1 hardware, 32-bit read-only
data
Count value after electronic gear, 32-bit
read-only data
1 to 4294967295, when the counter 1
count value (after the electronic gear)
reaches this setting, the DO function
"Counter 1 set value reached" is valid.
1 to 4294967295, set the maximum value
of counter 1 (after electronic gear)
1~65535
Counter 1 count value = counter 1 input
value ×( electronic gear numerator /
electronic gear denominator )
1~65535
- 120-
Default
Property
0
0
0
0
0
0
0
0
-
-
1000
429496729
5
1
1