VFD500 high performance vector control frequency inverter user manual Appendix A Modbus communication protocol
0x7001
Communication
special address
0x7002
0x7003
0x7004
0x7005
0x7006
0x7007
0x7008
0x7009
0x700A
0x700B
2)Inverter status: Read the inverter status, see 27 groups of function codes.
Decimal address: 27 × 256 + 10 = 6922.
Example 2: Function code 14.01 (digital setting of torque reference), when
no EEPROM is stored, its
The hexadecimal address is: 0x0E01 (0x0E = 14, 0x01 = 1),
The decimal address is: 14 × 256 + 1 = 3585.
If you want to save the content written in communication to EEPROM after
power off, then
The hexadecimal address is 0x8E01 (0x0E01 plus 0x8000),
The decimal address is 36353 (3585 plus 32768).
Note: The addresses calculated in hexadecimal or decimal are the same,
and users can choose a familiar calculation method.
Communication command. The values and functions are as follows:
0x0000:disable command ;
0x0001:forward running;
0x0002:reverse running;
0x0003:forward jog;
0x7000
0x0004:reverse jog;
0x0005:free stop;
0x0006:decelerating stop;
0x0007:immediate stop;
0x0008:fault reset;
Communication speed given. The unit of this register can be set by P30.14.
0.01%(-100.00% ~ 100.00%)
0.01Hz(0 ~ 600.00Hz)
1Rpm(0 ~ 65535Rpm)
Communication Torque given.0.01%(-300.00% ~ 300.00%)
Communication upper frequency given. The unit of this register can be set
by P30.14.
Different units range same as 0x7001.
Torque mode speed limit. The unit of this register can be set by P30.14.
Different units range same as 0x7001.
Electric torque limit 0.1%(0~300.0%)
Power generation torque limit 0.1%(0~300.0%)
PID setting source.0.01%(-100.00% ~ 100.00%)
PID feedback source 0.01%(-100.00% ~ 100.00%)
VF separation voltage given.0.1%(0~ 100.0%)
External fault setting
DO status setting. When the DO function (please refer to P07.01 ~ P07.10)
is set to 0 (no function), its status comes from the setting of the
communication dedicated register, and the corresponding bit of 1 means it
is valid. The bits of this register are defined as follows:
Bit7
Bit6
Bit15
Bit14
Bit5
Bit4
Bit13
Bit12
- 145-
Bit3
Bit2
Bit1
RL2
RL1
DO2
Bit11
Bit10
Bit9
VDO2
Bit0
DO1
Bit8
VDO1