Chapter 5 Function code
Function
Parameter name
code
P01.08
Upper limit frequency
P01.09
Lower limit frequency
Action when set
P01.10
frequency lower than
lower limit frequency
Delay time when set
P01.11
frequency lower than
lower limit frequency
Jump frequency start
P01.12
up protection
Jump frequency 1
P01.13
lower limit
Jump frequency upper
P01.14
limit
Jump frequency 2
P01.15
lower limit
VFD500 high performance vector control frequency inverter user manual
Description
3:Reserved
4:Reserved
5:Pulse setting HDI
6:Reserved
7:Communication setting
Lower limit frequency(P01.09)~maximum
frequency (P01.06)
0.00Hz~upper limit frequency
0:Run at low limit frequency
1:Stop after delaying P01.11
2:Run at zero speed
The inverter will coast to stop when the set
frequency is lower than the lower-limit one.if
the set frequency is above the lower limit one
again and it lasts for the time set byP01.11,
the inverter will come back to the running state
automatically.
0.000s~30.000s
This function code determines the hibernation
delay time. When the running frequency of the
inverter is lower than the lower limit one, the
inverter will stop to stand by.
When the set frequency is above the lower
limit one again and it lasts for the time set by
P01.11, the inverter will run automatically.
Unit/ten/hundred'digit:three jump frequency
1/2/3
0:Disable
1:Enable (avoid risk speed)
0.00Hz~(P01.14)
P01.13- (P01.06)Maximum frequency
0.00Hz~(P01.16)
- 42-
Default
Property
50.00Hz
0.00Hz
0
0.000s
000
0.00Hz
0.00Hz
0.00Hz