Chapter 5 Function code
Function
Parameter name
code
Speed Proportional
P13.00
Gain ASR_P1
Speed Integral Time
P13.01
constant ASR_T1
Speed Proportional
P13.02
Gain ASR_P2
Speed Integral Time
P13.03
constant ASR_T1
ASR parameter
P13.04
Switching frequency 1
ASR parameter
P13.05
Switching frequency 2
By setting the speed factor and integration time of the speed regulator, you can adjust
Section vector controlled speed loop dynamic response characteristics. Increase the proportional gain and reduce
The integration time can speed up the dynamic response of the speed loop, but the proportional gain is too large
Or the integration time is too small, it is easy to cause the system to oscillate, and the overshoot is too large.
Proportion increase
Too small is also likely to cause steady-state oscillations of the system, and there may be a speed difference.
PI has a close relationship with the inertia of the system. Adjust on the base of PI according to different loads to
meet various demands.
P13.00 and P13.01 are Speed adjuster parameter for low-speed use, scope of action from zero to P13.04
P13.02 and P13.03 are Speed adjuster parameter for high-speed use, scope of action from P13.05 to maximum
frequency
P13.04-P13.05 Two sets of parameter for linear transitions
Speed control torque
P13.06
limit source selection
VFD500 high performance vector control frequency inverter user manual
13 Group Motor 1 vector control
Description
0.1~100.0
0.001s~30.000s
0.1~100.0
0.001s~30.000s
0.00Hz~ ASR switching frequency
2(P13.05)
ASR switching frequency 1~
600.00Hz(P13.04)
Unit's digit:Electric torque limit source
0:Digital setting
1:Ai1
2:Ai2
3:AI3((IO expansion board)
4:Reserved
5: HDI
6:Communication
Ten'unit:Electric torque limit source
Same as unit'digit
- 77-
Default
Property
12.0
☆
0.200s
☆
10.0
☆
0.500s
☆
5.00Hz
☆
10.00Hz
☆