VFD500 high performance vector control frequency inverter user manual Appendix B Profinet communication card usage
(6)Operate the PZD data to start the first PN device, add Mov_W instructions (PZD
mapping data is 16 bits of data, word type).
7. Problems and Handling
The status and description of the indicator are as follows:
numbering
Symptom
A PN communication
failure has occurred
1
red
Green
Explanation
light
light
off
off
Working
on
off
PN
fault
flash
off
Inverter fault
On
On
Profinet
communication fault
Flash on
Configuration error
flash
flash
Blinking status
You can check whether the function code P30.02 is 2, if
not, please set it to 2; Whether the function code mapped
by PZD is correct; When writing a value to a function code,
whether the value is outside the range of the function code
- 176-