VFD500 high performance vector control frequency inverter user manual Appendix B Profinet communication card usage
the port of another device directly connected to the port, and release the mouse. Note that it must
be consistent with the network connection of the actual device, if the actual PLC is connected from
P1 to P1 of slave 1, and then from P2 of slave 1 to the next slave, then the same should be true
in the topology. Incorrect topology can lead to failure of the replacement function or even abnormal
communication (for MT500PN communication card, facing the indicator, P1 on the left and P2 on
the right)
3.After connecting all topologies, compile and download them to the PLC
6. SMART master configuration
This section briefly introduces the S7-20 0PLC master configuration for SMART (V2.6 and
above). The corresponding GSDML file of MT 500-profinet communication card is: GSDML-V2.31-
MICFIND-mt500-20190705. The last part of the file name of the GSDML file is the release time,
which may vary due to version updates.
6.1 Scan PLC
(1) Double-click to open the SMART software, display the following interface, click P LC->PLC->
select a suitable network card - > click Find to determine the network segment and IP address of
PLC