VFD500 high performance vector control frequency inverter user manual
Item
Torque control
accuracy
V/f curve
Frequency
giving ramp
DC bus voltage
control
Carrier frequency 1kHz~12kHz(Varies depending on the type)
Startup method Direct start (can be superimposed DC brake); speed tracking start
Stop method
Main control
function
Keypad
Communication
PG card
Input terminal
Function
Output terminal
Protection Refer to Chapter 6 "Troubleshooting and Countermeasures" for the protection function
Installation
location
Environment
Altitude
SVC:within 5Hz10%,above 5Hz5%
VC:3.0%
V / f curve type: straight line, multipoint, power function, V / f
separation;
Torque boost support: Automatic torque boost (factory setting),
manual torque boost
Support linear and S curve acceleration and deceleration;
4 groups of acceleration and deceleration time, setting range 0.00s ~
60000s
Overvoltage stall control: limit the power generation of the motor by
adjusting the output frequency to avoid skipping the voltage fault;
Undervoltage stall control: control the power consumption of the
motor by adjusting the output frequency to avoid yaw failure
VdcMax Control: Limit the amount of power generated by the motor
by adjusting the output frequency to avoid over-voltage trip;
VdcMin control: Control the power consumption of the motor by
adjusting the output frequency, to avoid jump undervoltage fault
Deceleration stop (can be superimposed DC braking); free to stop
Jog control, droop control, up to 16-speed operation, dangerous
speed avoidance, swing frequency operation, acceleration and
deceleration time switching, VF separation, over excitation braking,
process PID control, sleep and wake-up function, built-in simple PLC
logic, virtual Input and output terminals, built-in delay unit, built-in
comparison unit and logic unit, parameter backup and recovery,
perfect fault record, fault reset, two groups of motor parameters free
switching, software swap output wiring, terminals UP / DOWN. STO
(Safe Torque Off)
LED Digital keyboard and LCD keypad(option)
Standard:
MODBUS communication TCP protocol communication
CAN OPEN AND PROFINET
Incremental Encoder Interface Card (Differential Output and
Open Collector), Rotary Card , frequency division signal pg card
Standard:
5 digital input terminals, one of which supports high-speed pulse input
up to 50kHz;
2 analog input terminals, support 0 ~ 10V voltage input or 0 ~ 20mA
current input;
Option card:
4 digital input terminals
2 analog input terminals. support-10V-+10V voltage input
standard:
1 digital output terminal;
1 high-speed pulse output terminal (open collector type), support 0 ~
50kHz square wave signal output;
1 relay output terminal (second relay is an option )
2 analog output terminals, support 0 ~ 20mA current output or 0 ~
10V voltage output;
Option card: 4 digital output terminals
Indoor, no direct sunlight, dust, corrosive gas, combustible gas, oil
smoke, vapor, drip or salt.
0-3000m.inverter will be derated if altitude higher than1000m and
rated output current will reduce by 1% if altitude increase by 100m
- 8-
Chapter2 production information
Specification