Veikong VFD500-PV Operation Manual

Veikong VFD500-PV Operation Manual

Ries solar pump inverter
Hide thumbs Also See for VFD500-PV:

Advertisement

Quick Links

Operation manual
VFD500-PV/VFD500M-PV
Series
Solar Pump Inverter

Advertisement

Table of Contents
loading

Summary of Contents for Veikong VFD500-PV

  • Page 1 Operation manual VFD500-PV/VFD500M-PV Series Solar Pump Inverter...
  • Page 2: Table Of Contents

    Solar pumping inverter user manual Chapter 1 Electrical cable Connection ............1 Chapter 2 Motor Pump Connection ............7 Chapter 3 Keypad display ................. 17 Chapter 4 Solar pump special parameter User mode fast quick start ..21 Chapter 5 Detailed Parameter list ............. 26 Chapter 6 Fault Diagnosis and Solution ...........
  • Page 3: Chapter 1 Electrical Cable Connection

    Chapter 1 Electrical cable Connection 1.1 VFD500-PV Electrical cable Connection Please follow the diagram below for wiring. And pay attention to the following issues: Figure 1-1 SIZE A~SIZE C 0.75kw-15kw Main Circuit Terminal Figure 1-2 SIZE D 18.5kw-22kw main circuit terminal block diagram...
  • Page 4 Figure 1-5 SIZE H-K 110kw-250kw Figure 1-6 SIZE H-K 280kw-500kw Table 1-1 Function description of the main circuit terminal of the inverter Terminal Function instruction AC power input terminal, connect three-phase AC power or R、S、T Solar+ - U、V、W Inverter AC output terminal, connect three-phase AC motor The positive and negative terminals of the internal DC bus are +、- connected to the external brake unit or For common DC bus...
  • Page 5 1.2 VFD500M-PV Electrical cable Connection Please follow the diagram below for wiring. And pay attention to the following issues: Table 1-2 Function description of the main circuit terminal of the inverter Terminal Function instruction L1、L2、L3 AC power input terminal, or solar DC supply terminal U、V、W Inverter AC output terminal, connect three-phase AC motor +、-...
  • Page 6 DC voltage of inverter and Solar panel Vmp is recommend 530V for 380V pump and 305V for 220V pump. 1.4 Power degree AND Technical SPECIFICATION Power size of VFD500-PV refers to the standard 4 poles induction motor at rated voltage. Overload: 150% rated output current, 1 minute.
  • Page 7 Table 1-4 380V-480V rating data Applicable Max DC input Rated output Inverter model water pump current (A) current (A) (kW) VFD500M-40T00150-PV VFD500M-40T00220-PV VFD500M-40T00400-PV 16.5 VFD500M-40T00550-PV 23.9 VFD500M-40T00750-PV 30.6 VFD500-40T00150-PV VFD500-40T00220-PV VFD500-40T00400-PV 16.5 VFD500-40T00550-PV 23.9 VFD500-40T00750-PV 30.6 VFD50040T01100-PV 39.2 VFD500-40T01500-PV 49.0 VFD500-40T01850-PV 18.5 VFD500-40T02200-PV...
  • Page 8 Table 1-5 220V Single phase/Three phase level Applicable Max DC input Rated output Inverter model water pump current (A) current (A) (kW) VFD500-20T00075-PV 0.75 VFD500-20T00150-PV VFD500-20T00220-PV 14.1 10.6 VFD500-20T00400-PV 22.6 VFD500-20T00550-PV VFD500-20T00750-PV VFD500-20T01100-PV VFD500-20T01500-PV VFD500-20T01850-PV 18.5 VFD500-20T02200-PV VFD500-20T03000-PV VFD500-20T03700-PV VFD500M-20T00150-PV VFD500M-20T00220-PV 14.1 10.6...
  • Page 9: Chapter 2 Motor Pump Connection

    Chapter 2 Motor Pump Connection 2.1 For 380V or 220V or 110V Three phase motor pump connection Figure 2-1 VFD500-PV Wire Diagram of solar pump inverter (three phase pump)
  • Page 10 Figure 2-2 VFD500M-PV Wire Diagram of solar pump inverter (three phase pump) NOTE: 1:VFD500-PV/VFD500M Solar array output should be connected to the terminal ( +DC、-DC) of the drive,Grid connected L1 L2 L3 or RST terminal. 2: For control wire, recommend using shielded cable or shielded twisted pair.
  • Page 11 HDI input. Figure 2-3 Internal electrical schematic diagram of single-phase motor(with capacitor) Figure 2-4 VFD500-PV/500M-PV Wire Diagram of solar pump inverter (single phase pump with capacitor) 2.3 Single phase asynchronous motor wiring method (without starting capacitor):...
  • Page 12 P00.11=00031 if your motor frequency is 50 Hz or set P00.11=32 if your motor frequency is 60HZ. Figure 2-6 VFD500-PV/VFD500M-PV Wire Diagram of solar pump inverter (single phase pump without capacitor) 2.4 Wiring method for Compensation of Grid and Solar DC supply Under normal circumstances, the inverter does not allow AC and DC to be connected at the same time.
  • Page 13 Figure 2-7 Wiring diagram of main circuit for simultaneous photovoltaic and power supply 2.5 Control Circuit Terminal Figure 2-8 Diagram VFD500-PV control circuit terminal Table 2-1 VFD500-PV control circuit terminal instruction Terminal Terminal Type Terminal function description Symbol Name 10.10V±1%...
  • Page 14 Analog Internal isolation from COM ground Input voltage:0~10V:Impedance 22KΩ,Maximum input voltage Input current:0~20mA: Impedance 500Ω,Maximum Analog input current input1 Through the jumper switch AI1 0 ~ 10V and 0 ~ 20mA analog input switch, the factory default voltage input. Input voltage:0~10V:Impedance 22KΩ,Maximum input voltage Input current:0~20mA:...
  • Page 15 To provide 24V power supply, generally used as a digital input and output terminal power supply and external sensor power The factory default setting is connected PLC with +24V Digital input Terminal for on-off input high and low level switch terminal When using the external signal to drive DI1~DI5, it common...
  • Page 16 2.6 Trial run(How to start solar pump inverter) 2.6.1 set parameter Make sure all cables connections of solar panel and pump motor correct and no need to set any parameter, if you want to set parameter, you can do as follows. Step 1(Keypad control):Set motor parameter P11.02- P11.06 as per motor pump name plate If dry run protection is required, measure the unload protection current (see details in user manual chapter for dry run function) If dry run protection not required then miss this step and go to step 2.
  • Page 17 2.6.3Technical Questions and solutions (1) How to achieve Automatic start after stop? If it is controlled by keyboard, so there is no need to set any parameter (P47.03 waiting time) If you want to control by external switch. First set P00.06=1 and use a wire or switch to connect com and DI1,When the switch is closed, the drive run, when the switch is open, the drive stop.
  • Page 18 How to make the water pump system work without sunshine? Usually, solar PV water pump system can meet the needs of pumping water. If there is no sunshine, the system will not work. But out inverter could also support AC input. So, connect the power grid or diesel power generation to the inverter, the pumping system will work.
  • Page 19: Chapter 3 Keypad Display

    Chapter 3 Keypad display 3.1 LED Instruction of operation and display LED keyboard consists of 5 digital tubes, 7 lights, 8 keys and a potentiometer; can be used to set the parameters, status monitoring and operation control, LED keyboard shape as shown in Figure 3-1: Figure 3-1 Operating panel Description of indicator Table 3-1 The name and function of each part of the keyboard...
  • Page 20 • When it is on, the drive is faulty. 3.2 Display hierarchy and menu mode VFD500-PV digital keyboard display is divided into four layers, from top to bottom are: monitoring status, menu mode selection status, function code selection status, parameter editing / viewing status, as shown in Figure 4-2.
  • Page 21 Figure 3-2 Keyboard operation diagram 3.3 Monitor display(P21.00=1) According to the running status of the inverter, the digital tube displays different contents in turn. If the button has no operation, the next monitoring amount is automatically displayed every few seconds; of course, you can also switch to the next monitoring indicator ...
  • Page 22 Alarm code Meaning Light weak fault, please refer to function Sleep code P47.05~P47.07 Full water protection P47.18-47.21 A.FULL Low power protection P47.22-47.24 A.PoL Over current protection P47.25-47.27 A.oC Low water protection P47.33-47.36 A.Lor Dry dun protection see P24.12-24.14 PoFF Soft start status or insufficient power supply status when the drive starts For other alarm codes, please refer to Chapter 6 of the manual.
  • Page 23: Chapter 4 Solar Pump Special Parameter User Mode Fast Quick Start

    Chapter 4 Solar pump special parameter User mode fast quick start Function Name Description Default Property code 0:NO ACTION 11:Restore default parameter except for motor parameter and auto-tune related P00.03 RESET ★ parameter and factory parameter 12:Restore default to factory parameter 13:Clear tripping record 0:keypad Source of the...
  • Page 24 Upper limit Lower limit frequency-maximum P01.08 50.00Hz ☆ frequency frequency 0:No function 1:READY Relay 1 Output 2:RUN terminal function P07.03 3:Error1(stop fault) ☆ group (T1A T1B 4:Error2 ( same as Error1 except T1C) undervoltage) 5:Warning output(fault but in running) 0:Three phase AC asynchronous motor AC asynchronous P11.01 1:...
  • Page 25 3.1 in detail ) it show Hz, current, power and voltage Undervoltage 220V level: 160V~300V 220/380 P23.02 ★ threshold 380V level: 350V~520V Undervoltage 220V Level:160V~300V P23.05 200/260 ★ trip threshold 380V Level:350V~520V Output phase 0.0-25%, means output phase P23.15 ☆ loss function detections shielded Accumulative...
  • Page 26 Hundred’s unit automatic switching function 0:Disabled (Can be forced to switch ac grid through terminal function 62, invalid when enabled) 1:Automatically switch to Photovoltaic priority 2:Automatically switch to GRID power priority. When Automatic switching is enabled, and the light is weak, it will automatically switch to the electric supply, and the MPPT function is disabled at this time In auto start mode, set the time from...
  • Page 27 After the sleep fault is reported, if the time when Vdc is higher than the undervoltage point is greater than the set value, the fault Light weak wake state is exited and the operation continues. P47.07 600s ☆ up time When the automatic switching is enabled, after switching into the electric supply operation for this time, it will try to switch...
  • Page 28: Chapter 5 Detailed Parameter List

    Chapter 5 Detailed Parameter list Symbol Description: “☆” means that the set value of this parameter can be changed no matter the inverter is in the stop state or in running state. “★” indicates that the set value of this parameter cannot be changed while the inverter is running. “●”...
  • Page 29 when enabled) 1:Automatically switch to Photovoltaic priority. 2:Automatically switch to GRID power priority. When Automatic switching is enabled, and the light is weak, it will automatically switch to the electric supply, and the MPPT function is disabled at this time. Remarks: Inbuilt auto MPPT software and algorithm which measure and detect every 2ms to adjust current and voltage to find the best working maximum power The input of solar energy determines the frequency...
  • Page 30 If the output frequency is lower than this value and exceeds P47.06, it will be reported to Sleep and stop Light detection P47.05 20Hz ☆ threshold If automatic switching is enabled, it will switch to ac grid operation, and the MPPT function will be disabled This is light detection threshold to measure solar radiation and solar power in a setting time (P47.06 Detection time),if customer do not want to keep pump running below this frequency so it can make...
  • Page 31 P47.08 is mppt tracking step ,our solar pump inverter detect and adjust voltage and current every 2ms to search the best working maximum power to drive the pump ,we recommend the user understand this parameter and do not set and change without factory guidance ,the large in the value ,the faster the maximum power point is found ,but the accuracy of the maximum power is lower Regulator P47.09...
  • Page 32 4: AI4 Note: DI terminal 60-full water detection is independent of the local setting Ten’unit: Analog water level logic 0: Positive logic 0.00%-empty water 100.0%-full water 1: Inverse logic 0.00%-full water 100.0%-empty water Hundred’Unit: Double switch water level mode 0-Single switch mode 1-Filling mode, high water level stop, low water level start 2- Pumping mode, low water level stop,...
  • Page 33 When the tens digit of P47.18 is 1 and the analog input is less than the detection value, for example: set P47.18=11, P47.19=50%, then the AI1 input is less than 5V or 10mA. (4) After the conditions 1), 2) or 3) are met, the system reports A.FULL for the time set by P47.20. 2.
  • Page 34 0~1000s During operation, when the actual output Low power P47.23 10.0s power (r16.02) is less than P47.22 and the ☆ detection time time of P47.23 is maintained, the system reports A.Pol and stops. 0~1000s When the condition described in P47.23 Low power P47.24 10.0s...
  • Page 35 Function faults include: under-voltage fault Er.Lu1, soft start fault Er.Lu2, inverter overload Er.oL, motor overload Er.oL1, inverter overheat Er.oH, motor overheat Er.oH1, motor overheat Er.oH1, user-defined fault 1 Er .Ud1, user-defined fault 2 Er.Ud2 0~500V It is not recommended to modify, limit the PV reference voltage MPPT tracking reference voltage, and...
  • Page 36 0.0~3000.0s Low water P47.36 10.0s When the conditions described in P47.35 ☆ recovery time are not met, it will be restored after a delay Conditions for the water shortage test to take effect: 1. The DI terminal arbitrarily set to function No. 61 receives the input switch close signal. For example, after P06.04 is set to 61, DI4 is closed.
  • Page 37 Step length at startup is P47.08*P47.40, and it will return to P47.08 after reaching P47.40 Step length gain ☆ the MPPT point Note: only valid IN fast MPPT mode 1~300 Adjustment gain when the deviation between the bus voltage and the target voltage is small Fast MPPT P47.41...
  • Page 38 100~1000V After low light (Sleep), when the bus voltage is higher than the set value of P47.45, wake-up counting is performed. After low light Sleep, when the bus voltage Low light P47.45 is lower than the set value of P47.45, it will ☆...
  • Page 39 0: Do not detect mains power, turn off the switching board function 1:AI1, turn on the switching board Mains power function, AI1 is connected to the switching P47.54 ☆ detection channel board VGrid port 2: AI2, turn on the switching board function, AI2 is connected to the VGrid port of the switching board 0~1000V...
  • Page 40 When the units bit is selected as 0, the system is forced to switch to photovoltaic independent power supply; when it is selected as 1, the system is forced to switch to hybrid power supply; when it is selected as 2, the system automatically switches between photovoltaic independent power supply and hybrid power supply based on the detected photovoltaic voltage value and...
  • Page 41 Unload detection 0.00Hz~Fmax P24.15 5.00Hz ☆ offset frequency Detection frequency=Fmax-P24.15 Reset time of dry P24.16 240.0s 0.0~6000.0 ☆ run protection 0000:Coast stop Dry run detection P23.21 0000 1000:Fast stop ☆ mode 3000:Continue to run 1) Set P47.00=0, P00.07=20.00-30.00, P00.06=0, and then press to run the drive 2) Check the function code P27.00, wait until its value becomes 20.00, and then enter the function code P24.13,...
  • Page 42 2: AI2 wake up Hundred's digit: Sleep wake-up direction selection 0: positive direction Sleep source (AI1~AI2)>P41.03, inverter sleeps Wake-up source (AI1~AI2) <P41.04, the inverter wakes up 1: reverse direction Sleep source (AI1~AI2)<P41.03, inverter sleeps Wake-up source (AI1~AI2)>P41.04, the inverter wakes up Note: If AI2 is connected to the liquid level detection signal, please set this value to "23".
  • Page 43 0 ~ 65535  No user password status (P00.01 = 1 after power-on): Entering the same non-zero value twice in succession sets a user password and enters lockout.  password lock state: P00.00 User password ☆ Enter the password to enter the unlock state.
  • Page 44 8:PID 9:Internal PLC Notice: DI terminal function code 26-32 superior than this function code Maximum P01.06 10.00~600.00Hz 50.00Hz ★ frequency 0: Digital setting (P01.08) 1:AI1 2: AI2 Upper limit 3~4: reserved P01.07 ★ frequency control 5: HDI 6: reserved 7: Communication 8: PID Upper limit Lower limit frequency-maximum...
  • Page 45 0:No function 1:READY 2:RUN P07.01 DO1 function 3:Error1(stop fault) ☆ 4:Error2(same as Error1 except under-voltage) 5:Error 3(can continue ) 0:No function 1:READY 2:RUN 3:Error1(stop fault) P07.02 DO2 function ☆ 4:Error2(same as Error1 except under-voltage) 5:Error 3(can continue ) 47:Auto main & PV switching 0:No function 1:READY 2:RUN...
  • Page 46 DO1 ineffective P07.13 0.000s~30.000s 0.000s ☆ delay time DO2 effective P07.14 0.000s~30.000s 0.000s ☆ delay time DO2 ineffective P07.15 0.000s~30.000s 0.000s ☆ delay time Relay 1 effective Delay time from relay effective to actual P07.16 0.000s ☆ delay time action Relay 1 invalid The delay time from the deactivation of the P07.17...
  • Page 47 2 The interference generated by the inverter has an impact on peripheral devices 3 Long wiring distance between inverter and motor The carrier frequency can be increased when it came like following phenomenon: 1 The electromagnetic noise generated by the motor is large 0:effective when running 1:Forced control( effective when power Cooling method...
  • Page 48  Unit’digit :Over-voltage stall control 0:over-voltage stall disabled 1:over-voltage stall enabled 2:over-voltage stall enabled self-adjustable The over-voltage stall function limits the amount of power generated by the motor by extending the deceleration time or even increasing the speed, avoiding over-voltage on the DC side and reporting over-voltage faults ...
  • Page 49 Under-voltage P23.06 fault detection 0.0s~30.0s 1.0s ☆ time Output phase loss 0.0-25%, 0% means output phase P23.15 ☆ function detection shielded Define as per bit: bit0-undervoltage; bit1- inverter overload; bit2-inverter overheat ; P23.24 Fault reset bit3-motor overload ☆ bit4-motor overheat; bit5-user’fault 1;...
  • Page 50 Fault auto reset P23.29 times clearing 0.1s~3600.0s 600.0s ☆ time 11 Group Motor 1 Parameter 0:AC asynchronous motor P11.00 Motor type ● 1:Synchronous motor(Special software) See appendix parameter 0:Three phase AC asynchronous motor AC asynchronous P11.01 1:Single phase AC asynchronous motor ★...
  • Page 51 0:no auto tuning 1:Stationary auto tuning of Asynchronous motor It is suitable in the cases when the motor can not decouple form the load. The auto tuning for the motor parameter will impact Auto-tune/self-lea P11.10 the control accuracy. ★ rning 2:dynamic or Rotational auto tuning of Asynchronous motor Comprehensive motor parameter auto tune...
  • Page 52 Figure 5-1 Motor overload protection starting current Figure 5-2 Motor Overload Protection Curve with Different Overload Protection Gains Motor overload only protects the motor from overload when P24.04 is enabled.P24.00 is used to adjust the overload inverse time curve time, as shown in the right figure above, the minimum motor overload time is 5.0s.
  • Page 53 bit0:direction of running frequency bit1:direction of setting frequencybit2: Direction direction of main frequency r27.02 ● indicator bit3:direction of auxiliary frequency bit4:direction of Up Down offset bit5: reserved r27.03 DC Bus voltage Unit:1V ● VF separation r27.04 unit:0.1% ● setting Output AC r27.05 unit:0.1V ●...
  • Page 54 25 Group Fault tracking parameter See detail chapter 5 fault diagnosis and r25.00 Current fault type ● solution Output frequency r25.01 Unit:0.01Hz ● at fault Output current at r25.02 Unit:0.1A ● fault Bus voltage at r25.03 Unit: V ● fault Running mode r25.04 See Parameter r27.10 in detail...
  • Page 55 Output frequency r26.01 Unit:0.01Hz ● at fault Output current at r26.02 Unit:0.1A ● fault Bus voltage at r26.03 Unit: V ● fault Running mode r26.04 See Parameter r27.10 ● status 1at fault Input terminal Bit0~Bit6 corresponds to DI1~DI7 r26.05 ● status at fault Bit12~Bit15 corresponds to VDI1~VDI4 Working time at...
  • Page 56 Output frequency r26.17 Unit:0.01Hz ● at fault Output current at r26.18 Unit:0.1A ● fault Bus voltage at r26.19 Unit: V ● fault P40 PID Group PID final output r40.00 Read only unit:0.1% ● value PID final set r40.01 Read only:0.01% ●...
  • Page 57 PID digital setting P40.06 0.0~P40.05 0.00 ☆ Unit’s digit 0:PID feedback source1(fdb1) 0:AI1 1:AI2 2:AI3(option card) 3:AI4(option card) 4: PLUSE(HDI) PID feedback P40.11 5: Communication ☆ source1 6: Motor rated output current 7: Motor rated output frequency 8: Motor rated output torque 9: Motor rated output frequency Ten’s digit : PID feedback source2 (fdb2) Same as Unit’s digit...
  • Page 58 2:Curve C 3:Curve D Ten ‘unit:when input signal lower than minimum input 0:equal to minimum input 1:equal to 0.0% P04.08 AI1 filter time 0.000s~10.000s 0.100s ☆ 0.00V~10.00V ( it is used to view the port voltage of AI1. When AI1 is a current type r04.09 ●...
  • Page 59 0.00V~ P04.25 Curve A P04.23 horizontal 0.00V ☆ axis 1 -100.0%~ Curve A vertical 100.0% P04.24 0.0% ☆ Note: Input less than P04.23, axis 1 output decided by curve ten’s digit. Curve A Setting method mode for AI1 P04.23~ P04.25 horizontal 10.00V ☆...
  • Page 60 2. Set the function code: P04.11 one place=1 (default), P04.27=2.00 06 Group Digital input (Terminal function) 0:No function 1:Run terminal DI1 functional 2: Reverse/Forward and reverse switchover P06.01 ★ selection 3:Three wire control 4:Forward jog command 5:Reverse jog command 6:Terminal UP 7:Terminal DOWN DI2 functional P06.02...
  • Page 61 high-frequency pulse input 32:Switch main frequency source to communication setting 33:Switch auxiliary frequency source to numeric frequency setting 60: full water level detection 61: Water shortage alarm 62: Forced switching to ac power...
  • Page 62: Chapter 6 Fault Diagnosis And Solution

    Chapter 6 Fault Diagnosis and Solution VFD500-PV inverter has 24 types of warning information and protection function. In case of abnormal fault, the protection function will be invoked, the inverter will stop output, and the faulty relay contact of the inverter will start, and the fault code will be displayed on the display panel of the inverter.
  • Page 63 Fault Fault Name Solutions Display Possible Causes code 1: Eliminate external faults. 1: The output circuit is grounded or 2: Perform the motor auto- short circuited. Tuning in cold state. 2: Motor auto-tuning is not 3: Increase the acceleration performed. time.
  • Page 64 Fault Fault Name Solutions Display Possible Causes code 1: The output circuit is grounded or 1:Eliminate external faults. short circuited. 2: Perform the motor 2: Motor auto-tuning is not auto-tuning. performed. 3:Adjust The voltage to Over current Er.OC3 at constant normal range.
  • Page 65 Fault Fault Name Solutions Display Possible Causes code 1:the power supply voltage 1:The input voltage is too high is reduced to the normal 2:The surge voltage is mixed in the range input power supply. 2:install DC reactor 3: There is an external force to drive 3:Cancel the external force Overvoltage Er.OU3...
  • Page 66 Fault Fault Name Solutions Display Possible Causes code 1:Check if the input power supply is abnormal, whether the input power terminal is 1: Instantaneous power failure loose, whether the input occurs contactor or the air switch is on the input power supply abnormal.
  • Page 67 Fault Fault Name Solutions Display Possible Causes code 1. Reduce the load and check the motor and mechanical conditions. 1:The load is too large or the motor Correctly set the motor is blocked. parameters and motor 2:The large inertia load acceleration protection parameters.
  • Page 68 Fault Fault Name Solutions Display Possible Causes code 1:Lower the ambient 1: The ambient temperature is too temperature. high. 2: Clean the air filter. 2: The air filter is blocked. 3: Replace the damaged fan. 3: The fan is damaged. IGBT Module Er.
  • Page 69 Fault Fault Name Solutions Display Possible Causes code 1. Check the thermistor 1,Temperature detection line broken wiring 2, Drive board is faulty Module 2.Ask for technical support Er.tCK temperature 3. Main control board is faulty 3.Ask for technical support detection fault 4, The environmental temperature is 4.
  • Page 70 Fault Fault Name Solutions Display Possible Causes code 1: Set the motor parameters according to the nameplate 1: The motor parameters are not set properly. Motor Er.tU1 auto-tuning according to the nameplate. 2: Check the cable fault 1 connecting between the 2: The motor auto-tuning times out.
  • Page 71 Fault Fault Name Solutions Display Possible Causes code 1: The signal of user-defined fault 1 is input via DI. 1: Reset the operation. User-defined Er.Ud1 fault 1 2:The signal of user-defined fault 1 2: Reset the operation is input via virtual I/O. 1: The signal of user-defined fault 2 is input via DI.
  • Page 72: Chapter 7 Service Agreement

    Not permitted by the factory supplier, modified the drive devices;  Out of the VFD500-PV product specification application;  Failure consequences by fire, flooding, earthquake etc., unforesee natural disasters;...
  • Page 73 Solar pump inverter maintenance warranty card User corporation: Address: Post Code: Contractor: Tel. No.: Fax No.: Solar pump inverter type: Product Information Power size(kW): S.N.: Contract No.: Purchase date: Service engineer: Tel. No.: Repair record Fixed date: Fault information: Complaints and demanding on our products: User signature: year month...
  • Page 74: Appendix A Ac/Dc Switching Scheme

    A.1.1 Installation and dimensions The dimensions of the switching board of the VFD500-PV series are shown in Figure C-2. When installing the switch board inside the control cabinet, you can use the four screw positions on the back of the switch board to fix it.
  • Page 75 Figure A-2 Photovoltaic switching board wiring diagram Table A-1 Switching board terminal description Terminal Terminal Name Terminal Function Description Symbol PV detection input, connect the positive and PV+ ,PV- Photovoltaic input negative poles of the photovoltaic input Mains power or generator AC detection input, connected to any two phase L1,L2 detection input...
  • Page 76 Other-intermediate working status After checking that the wiring between the switching board and VFD500-PV is correct, close the AC and DC circuit breakers (in no particular order) and set the function codes shown in Table C-3 to start the inverter.
  • Page 77 1:AI1, turn on the switching board function, AI1 is connected to the Mains power detection VGrid port of the switching board P47.54 channel 2: AI2, turn on the switching board function, AI2 is connected to the VGrid port of the switching board voltage corresponding to the maximum Switch to photovoltaic...
  • Page 78 Remark: [1] Solar panel active: PV voltage r47.50 is greater than the threshold setting P47.56 for switching to hybrid power supply. [2], [6] The driver works in photovoltaic independent power supply mode/hybrid mode: it can be checked through function code r47.58. [3] The output frequency is too low and has been maintained for a period of time: the operating frequency r27.00 is less than the weak light detection threshold P47.05, and the duration exceeds the weak light detection time P47.06.
  • Page 79 [5] The sleep time is reached: the bus voltage r27.03 is greater than the weak light wake-up voltage P47.45, and the sleep time exceeds the weak light wake-up time r47.07. [7] The photovoltaic voltage is high enough and has been maintained for a period of time: the photovoltaic voltage r47.50 is greater than the switching to photovoltaic independent power supply threshold setting P47.55, and the duration exceeds the weak light wake-up time r47.07.
  • Page 80 VFD500-40T16000-PV 550A/ 550A/1600V 1000VDC VFD500-40T18500-PV 600A/ VFD500-40T20000-PV 600A/1600V 1000VDC VFD500-40T22000-PV 630A/ 630A/1600V 1000VDC VFD500-40T25000-PV VFD500-40T28000-PV 800A/ 800A/1600V 1000VDC VFD500-40T31500-PV VFD500-40T35500-PV 1000 1000 1000A/ 1000A/1600V 1000VDC VFD500-40T40000-PV 1000 1000 VFD500-40T45000-PV 1250 1250 1250A/ 1250A/1600V 1000VDC VFD500-40T50000-PV 1250 1250 Three phase voltage: 220V,50/60Hz VFD500-20T00040-PV 16A/ VFD500-20T00075-PV...
  • Page 81: Appendix B Recommended Solar Cell Module Configuration

    Appendix B Recommended solar cell module configuration Solar module open circuit voltage rating Number of Number of Inverter model Componen component Componen component t power s per string t power s per string * number * number (Wp) (Wp) of strings of strings Three phase voltage: 380V,50/60Hz VFD500-40T00075-PV...
  • Page 82 VFD500-40T20000-PV 21*39 18*38 VFD500-40T22000-PV 21*42 18*41 VFD500-40T25000-PV 21*48 18*47 VFD500-40T28000-PV 21*54 18*53 VFD500-40T31500-PV 21*60 18*59 VFD500-40T35500-PV 21*68 18*67 VFD500-40T40000-PV 21*77 18*75 VFD500-40T45000-PV 21*86 18*84 Three phase voltage: 220V,50/60Hz VFD500-20T00040-PV 11*1 VFD500-20T00075-PV 11*1 VFD500-20T00150-PV 11*1 VFD500-20T00220-PV 11*1 VFD500-20T00400-PV 11*2...
  • Page 83: Appendix C Gprs Module And Monitoring App

    Appendix C GPRS module and monitoring APP Figure C-1 GPRS module and inverter connection method Table C-1 Switching module terminal description Terminal symbol Terminal name Terminal function description GPRS module VCC is connected to the driver 24V, GND is connected VCC、GND power input to the driver COM...
  • Page 84 ShenZhen VEIKONG Electric CO., Ltd. Factory Address: 4F, Building 5, Dongluyang Industrial ,Park, No. 4, Tengfeng 4th Road, Fuyong Phoenix Third, Industrial Zone, Baoan District, Shenzhen Technical Support Hotline: +86-0755-89587650 Web Site: www.veikong-electric.com 008615989436541...

This manual is also suitable for:

Vfd500m-pv

Table of Contents